ABBRA INSTALLATION 

Panic / 24 Hours - 8 users

 

User No. 

 

Panic CP 

Duress

 

 

1

st

 digit

 

2

nd

 digit

 

Arm HOME

 

and AWAY (Closing) 

User No. 

 

Cancel alarm 

Recent Close 

1

st

 digit

 

2

nd

 digit

 

Disarm (Opening) 

User No. 

 

1

st

 digit

 

2

nd

 digit

 

Trouble 

Event 

 

Fuse 

Fail 

Fuse 

Restore 

Jamming  Jamming 

Restore 

AC 

Failure 

AC 

Restore 

CPU Low 

Battery 

CPU Low 

Battery Restore 

CP 

Tamper 

1

st

 digit

 

2

nd

 digit

 

 

 

Event 

 

CP Tamper 

Restore 

No Active 

COMM. & 

LINE Restore 

Enter Test 

Exit Test 

Auto Test 

1

st

 digit

 

2

nd

 digit

 

 
Understanding the Scancom Reporting Protocol Data Format 

The SCANCOM data format consists of 13 decimal digits divided 
into 4 groups, from left to right, as shown at the right side. 
Each channel is associated with a specific event as follows: 

1

st

 "C": 

Fire           

5

th

 "C":

 Alarm cancel 

2

nd

 "C": 

Personal attack 

6

th

 "C":

 Emergency 

3

rd

 "C": 

Intruder         

7

th

 "C":

 Second alarm 

4

th

 "C": 

Open/close     

8

th

 "C":

 Trouble messages 

aaaa     cccc     cccc  s

Account

Code

Channels

1 - 4

Channels

5 - 8

System Status:

no trouble,

test, low battery

The digit in this position conveys

the status of channel 1

The digit in this position conveys

the status of channel 8

 

Scancom Data Format

 

 

 

APPENDIX D. Programmable Zone Types 

D1. Delay Zones 

A  delay  zone  has  exit  and  entry  delays  set  by  you  in  the 
course  of  programming  the  system.  Warning  beeps  will 
sound throughout these delays, unless you choose to mute 
them. 

 

Exit  Delay 

-  The  exit  delay  begins  once  the  user  arms 

the system. It allows him to leave via interior zones and a 
doorway  before  arming  actually  takes  effect.  When  the 
exit delay starts, the buzzer beeps slowly and maintains a 
slow beeping rate until the last 10 seconds, during which 
it beeps rapidly. The Abbra has two types of delay zones, 
for which different delay times may be set. 

 

Entry  Delay

  -  The  entry  delay  begins  once  the  user 

enters  the  protected  area  via  a  specific  doorway  (his 
entry  is  sensed  by  a  delay  zone  detector).  To  avoid  an 
alarm,  he  must  reach  the  keypad  via  interior  zones 
(which  become  "follower  zones"  during  the  entry  delay) 
and  disarm  the  system  before  the  delay  expires.  When 
the  entry  delay  starts,  the  buzzer  beeps  slowly  until  the 
last 10 seconds, during which it beeps rapidly. 

D2. Emergency Zones  

You can provide incapacitated, sick or elderly people with a 
miniature single-button transmitter to be carried on the neck 
like  a  pendant  or  to  be  worn  on  the  wrist  like  a  watch.  In 
distress  situations,  they  can  press  the  button  on  their 
transmitter, causing the Abbra to send an 

emergency call

 

to  the  central  monitoring  station  or  to  private  telephones 
designated by the installer. 

To make this possible, define the required number of zones 
as  emergency  zones  and  enroll  a  portable  transmitter  to 
each one of these zones. When completed, ask the master 
user to distribute these transmitters to their potential users. 

D3. Fire Zones 

A  fire  zone  uses  smoke  detectors  and  is  permanently 
active  (a  fire  alarm  is  triggered  regardless  of  whether  the 
system is armed or disarmed). Upon detection of smoke, a 

pulsating  siren

  sounds  immediately  and  the  event  is 

reported via the telephone line.

 

Содержание Fully Supervised Wireless Alarm Control...

Страница 1: ...liminary Guidance 11 4 4 2 Entry Delays 1 2 11 4 4 3 Exit Delay 11 4 4 4 Bell Time 11 4 4 5 Abort Time 11 4 4 6 Alarm Cancel 11 4 4 7 Quick Arm 12 4 4 8 Bypass 12 4 4 9 Exit Mode 12 4 4 10 Piezo Beeps...

Страница 2: ...o the master user after testing the system Appendices A 1 and A 2 will help you prepare an installation plan Please take time to fill out the forms your job will become much easier and confusion will...

Страница 3: ...m in accordance with zone attributes Siren Signals Continuous intrusion 24 hours panic triple pulse pause triple pulse fire Siren bell Timeout Programmable 4 min by default Internal Sounder Output At...

Страница 4: ...to Pager PIN No Alarm Type Zone No 2 5 Physical Properties Operating Temp Range 32 F to 120 F 0 C to 49 C Storage Temp Range 4 F to 140 F 20 C to 60 C Humidity 85 relative humidity 30 C 86 F Size 10...

Страница 5: ...NSTALLATION GUIDE Version 04 4 12 17 5 Figure 3 1 Backup Battery Installation Open cover 1 Keypad cover 2 Remove screw and open battery compatment Remove screw to release wall mount bracket Connect ba...

Страница 6: ...6 ABBRA INSTALLATION Figure 3 2 Mounting the Control Panel...

Страница 7: ...ries has simple phone X 10 and AC power jacks pre installed No power or phone wiring is required simply plug the AC power cord into the AC power jack the phone cord into the telephone jack and the X 1...

Страница 8: ...1 3 8 Connecting Abbra to Computer The control panel can be equipped with an optional RS232 module for serial data interchange with a local computer If this module is not supplied a special plastic c...

Страница 9: ...reless siren Before beginning gather all the devices that you intend to enroll and make sure they all have batteries installed Your control panel must recognize the unique identification code ID of ea...

Страница 10: ...rolling action NEXT OK ENROL WL SIREN NEXT WL siren No 1 or 2 e g 2 SIREN No siren No 2 siren No 2 OK OK OFF TO DELETE Momentarily press the wireless siren self test button until a squawk is heard 1 s...

Страница 11: ...lumns even before you start and proceed to program according to your own list Remember A delay zone is also a perimeter zone by definition Zone types are fully explained in Appendix D For UL installat...

Страница 12: ...ing which the beeping rate increases Locations No 1 entry delay 1 and 2 entry delay 2 allow you to program the length of these delays Available options for each delay are 00s 15s 30s 45s 60s 3m and 4m...

Страница 13: ...rs after having been bypassed if the system remains armed The available options are shut after 1 shut after 2 shut after 3 and no shutdown In UL installations No Shutdown must be selected 4 4 14 Cross...

Страница 14: ...ted The available options are enable and disable 4 4 28 Disarm Option fig 4 4 location 28 Here you determine when it is possible to disarm the system A Any time B During entry delay by using the Abbra...

Страница 15: ...entry dly1 30 s entry dly1 45 s entry dly1 60 s entry dly1 3 m entry dly1 4 m abort time 00 s abort time 15 s abort time 30 s abort time 45 s abort time 60 s abort time 2 m abort time 3 m restart exit...

Страница 16: ...its 5 seconds F 5 Not applicable in phone numbers To enter a series of digits use the following keys Numeric keypad to enter the number Next Item moves the cursor from left to right Back moves the cur...

Страница 17: ...he pager s address The paging company s computer needs this input for routing messages to the specific pager The PIN sequence precedes any digital message that the Abbra sends to the pager to report a...

Страница 18: ...talled or not installed Available options are installed or not installed 4 6 2 1st 2nd 3rd 4th SMS Number Here you define the first second third and fourth SMS phone number including area code 16 digi...

Страница 19: ...3 Defining INT STRB Here you determine if the INT output will be used for an internal siren or for a strobe 4 7 4 X 10 GENERAL DEF Not evaluated by UL For X 10 devices you can select the following act...

Страница 20: ...PGM NEXT PGM NEXT Dxx BY ARM AWAY Dxx BY ARM HOME Dxx BY MEMORY OK ONE WAY UNIT PLEASE WAIT test fail test OK NEXT TWO WAY UNIT OK OK OK OK to Enroll enroll OK Enroll FAIL enroll fail HOME Exit X 10...

Страница 21: ...e fig 4 3 The recording process is shown below NEXT OK HOUSE IDENTITY 8 RECORD SPEECH see figure 4 1a USER 5 NAME NEXT USER 6 NAME NEXT USER 7 NAME NEXT USER 8 NAME RECORDING ENDED TALK NOW RECORD A M...

Страница 22: ...m does not recognize your installer code this indicates you must have programmed a user code that is identical with your installer code If so access the user menu and change the code that is identical...

Страница 23: ...roper function of all detectors in the system a comprehensive diagnostic test is required To perform this test refer to figure 4 9 5 3 Keyfob Transmitter Test Initiate transmission from each transmitt...

Страница 24: ...tery pack correct insertion and tightened battery compartment lid the TROUBLE indicator should extinguish However the MEMORY message will now blink in the display caused by the tamper alarm you trigge...

Страница 25: ...12 Flood 13 Interior Zone Locations Note down the intended location for each detector When programming you may select one of 26 available zone names plus 5 custom zone names that you can add see Figur...

Страница 26: ...ist Tx Transmitter Type Enrolled to Zone Name of holder Assignment 1 2 3 4 5 6 7 8 9 10 APPENDIX B X 10 Unit and PGM Output Assignments Unit Controlled ON ON ON ON ON ON ON by Timer ON by Zone No ON N...

Страница 27: ...od alarm restore FT Fire Detector Clean XR Sensor Battery Restore FJ Fire detector trouble XT Sensor Battery Trouble FR Fire Restore YR System Battery Restore GA Gas alarm YT System Battery Trouble Di...

Страница 28: ...ou choose to mute them Exit Delay The exit delay begins once the user arms the system It allows him to leave via interior zones and a doorway before arming actually takes effect When the exit delay st...

Страница 29: ...nd anti tamper protection They therefore trigger an alarm in both armed and disarmed states 24 Hour Zone Silent Upon detection this zone initiates a silent alarm meaning that the sirens do not functio...

Страница 30: ...and HOME together for 2 sec initiates PANIC alarm Pressing AWAY for 2 sec initiates Latchkey arming DISARM AWAY AUX HOME MCT 234 B MCT 231 201 N A in North America Single button pendant units The MCT...

Страница 31: ...e to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 0 To be certain of the number of devices that may be connected to the line as determined by the total RENs...

Отзывы: