Abbra Fully Supervised Wireless Alarm Control... Скачать руководство пользователя страница 24

24 

ABBRA INSTALLATION 

Go over the table in 

Appendix B

 column by column. If, for 

instance, the “

BY ARM AWAY

” column has “X”s marked in 

the  rows pertaining to units 1, 5 and 15 - then arm AWAY 
the  system  and  verify  that  the  appliances  controlled  by 
these units are actually activated upon arming.  
Continue  in  the  same  manner  in  the  following  columns, 
always  creating  the  state  or  event  that  will  activate  the 
relevant  units.  Verify  that  all  appliances  are  activated  as 
programmed. 

IMPORTANT!

  Before  testing  “BY  TIMER”  and  “BY 

ZONE”,  make  sure  that  these  forms  of  control  are 
permitted  -  press 

 

repeatedly  and  verify  that  the 

display shows: 

 

B Y   T I M E R   O N        

 

 

and: 

 

B Y   S E N S O R   O N      

 

A  dark  box  at  the  extreme  right  means  that  these 
functions are enabled. 

The  easiest  way  for  test  timed  activation  is  to  select  the 
ninth item in the installer’s menu (”

10. USER SETTINGS

”) 

and set the system clock a few minutes before the relevant 
“start time”. Do not forget to return the clock to the correct 
time after completion of this test. 

5.5 Emergency Transmitter Test  

Initiate  transmission  from  each  transmitter  enrolled  to  an 
emergency  zone  (according  to  the  list  in  Table  A3, 
Appendix  A).  For  example,  upon  pressing  the  transmit 
button of an emergency transmitter enrolled to zone 22, the 
display should read:  

 

Z 2 2       E M E R G E N C Y  

  (alternating)   

 

 

V I O L A T E D  

It  is  advisable  to  let  the  central  station  know  that  you  are 
conducting  this  test,  or  just  disconnect  the  telephone  line 
from the Abbra during the test, to prevent false alarms. 

 

6. MAINTENANCE 

6.1 Dismounting the Control Panel 

A.

 Release  the  Abbra  unit  from  its  bracket,  as  shown  in 

figure 3.2, step 1-3. 

B.

 Separate the Abbra unit from its bracket.

 

6.2 Replacing the Backup Battery 

Replacement  and  first-time  insertion  of  battery  pack  is 
similar (see figure 3.1).  
With  fresh  battery  pack,  correct  insertion  and  tightened 
battery  compartment  lid,  the  TROUBLE  indicator  should 
extinguish.  However,  the  “MEMORY”  message  will  now 
blink  in  the  display  (caused  by  the  “tamper”  alarm  you 
triggered when opening the battery compartment lid). Clear 
it by arming the system and immediately disarming. 

6.3   Fuse Replacement 

The  Abbra  has  two  internal  fuses  that  have  automatic 
reset. Therefore, there is no need to replace fuses. 
When  overcurrent  condition  occurs,  the  fuse  cuts  off  the 
circuit  current. Upon fault current  being removed, the fuse 
is  automatically  reset  and  allows  current  flow  through  the 
circuit again. 

6.4 Replacing/Relocating Detectors 

Whenever  maintenance  work  involves  replacement  or  re-
location  of  detectors,  always  perform 

a  full  diagnostic 

test according to par. 4.9.

  

Remember! 

A  "poor"  signal  is  not  acceptable,  as  stated 

at the end of the test procedure. 

 

7. READING THE EVENT LOG 

Up  to  100  events  can  be  stored  the  event  log.  You  can 
access  this  log  and  review  the  events,  one  by  one.  If  the 
event log fills up completely (100 events), the oldest event 
is deleted upon registration of each new event.  
The

 

date

 

and

 

time

 

of

 

occurrence

 

are

 

memorized

 

for

 

each

 

event.  

When  reading  the  event  log,  events  are  shown  in 
chronological order - from the newest to the oldest. Access 
to  the  event  log  is  provided  by  pressing  the 

  key  and 

not  through  the  installer’s  menu.  Reading  and  erasing 
process of the event log is shown in the next drawing. 

 

+

OK

+

OK

Oldest Event

Latest Event

LIST OF EVENTS

+

OK

CODE _ _ _ _

+

(Enter 4-digit

installer code)

(*)

(**)

<OK TO EXIT

CLEAR EVENT LOG

NEXT

+

NEXT

+

+

<OFF> TO DELETE

NEXT

+

NEXT

+

(Return to normal

operation)

OK

+
+

(***)

 

Figure 7 -  Reading / Erasing the Event Log 

*  

While the system is in normal operation mode, press 

 to review the event log. 

** 

Event  is  displayed  in  2  parts,  for  example,  "Z13  alarm"  then  "09/02/00  3:37  P".  The  two  displays  will  be  shown 
alternately until pressing OK again to move to the next event or until the end of the event log (4 minutes). 

***  Applicable only if installer code is entered.

 

Содержание Fully Supervised Wireless Alarm Control...

Страница 1: ...liminary Guidance 11 4 4 2 Entry Delays 1 2 11 4 4 3 Exit Delay 11 4 4 4 Bell Time 11 4 4 5 Abort Time 11 4 4 6 Alarm Cancel 11 4 4 7 Quick Arm 12 4 4 8 Bypass 12 4 4 9 Exit Mode 12 4 4 10 Piezo Beeps...

Страница 2: ...o the master user after testing the system Appendices A 1 and A 2 will help you prepare an installation plan Please take time to fill out the forms your job will become much easier and confusion will...

Страница 3: ...m in accordance with zone attributes Siren Signals Continuous intrusion 24 hours panic triple pulse pause triple pulse fire Siren bell Timeout Programmable 4 min by default Internal Sounder Output At...

Страница 4: ...to Pager PIN No Alarm Type Zone No 2 5 Physical Properties Operating Temp Range 32 F to 120 F 0 C to 49 C Storage Temp Range 4 F to 140 F 20 C to 60 C Humidity 85 relative humidity 30 C 86 F Size 10...

Страница 5: ...NSTALLATION GUIDE Version 04 4 12 17 5 Figure 3 1 Backup Battery Installation Open cover 1 Keypad cover 2 Remove screw and open battery compatment Remove screw to release wall mount bracket Connect ba...

Страница 6: ...6 ABBRA INSTALLATION Figure 3 2 Mounting the Control Panel...

Страница 7: ...ries has simple phone X 10 and AC power jacks pre installed No power or phone wiring is required simply plug the AC power cord into the AC power jack the phone cord into the telephone jack and the X 1...

Страница 8: ...1 3 8 Connecting Abbra to Computer The control panel can be equipped with an optional RS232 module for serial data interchange with a local computer If this module is not supplied a special plastic c...

Страница 9: ...reless siren Before beginning gather all the devices that you intend to enroll and make sure they all have batteries installed Your control panel must recognize the unique identification code ID of ea...

Страница 10: ...rolling action NEXT OK ENROL WL SIREN NEXT WL siren No 1 or 2 e g 2 SIREN No siren No 2 siren No 2 OK OK OFF TO DELETE Momentarily press the wireless siren self test button until a squawk is heard 1 s...

Страница 11: ...lumns even before you start and proceed to program according to your own list Remember A delay zone is also a perimeter zone by definition Zone types are fully explained in Appendix D For UL installat...

Страница 12: ...ing which the beeping rate increases Locations No 1 entry delay 1 and 2 entry delay 2 allow you to program the length of these delays Available options for each delay are 00s 15s 30s 45s 60s 3m and 4m...

Страница 13: ...rs after having been bypassed if the system remains armed The available options are shut after 1 shut after 2 shut after 3 and no shutdown In UL installations No Shutdown must be selected 4 4 14 Cross...

Страница 14: ...ted The available options are enable and disable 4 4 28 Disarm Option fig 4 4 location 28 Here you determine when it is possible to disarm the system A Any time B During entry delay by using the Abbra...

Страница 15: ...entry dly1 30 s entry dly1 45 s entry dly1 60 s entry dly1 3 m entry dly1 4 m abort time 00 s abort time 15 s abort time 30 s abort time 45 s abort time 60 s abort time 2 m abort time 3 m restart exit...

Страница 16: ...its 5 seconds F 5 Not applicable in phone numbers To enter a series of digits use the following keys Numeric keypad to enter the number Next Item moves the cursor from left to right Back moves the cur...

Страница 17: ...he pager s address The paging company s computer needs this input for routing messages to the specific pager The PIN sequence precedes any digital message that the Abbra sends to the pager to report a...

Страница 18: ...talled or not installed Available options are installed or not installed 4 6 2 1st 2nd 3rd 4th SMS Number Here you define the first second third and fourth SMS phone number including area code 16 digi...

Страница 19: ...3 Defining INT STRB Here you determine if the INT output will be used for an internal siren or for a strobe 4 7 4 X 10 GENERAL DEF Not evaluated by UL For X 10 devices you can select the following act...

Страница 20: ...PGM NEXT PGM NEXT Dxx BY ARM AWAY Dxx BY ARM HOME Dxx BY MEMORY OK ONE WAY UNIT PLEASE WAIT test fail test OK NEXT TWO WAY UNIT OK OK OK OK to Enroll enroll OK Enroll FAIL enroll fail HOME Exit X 10...

Страница 21: ...e fig 4 3 The recording process is shown below NEXT OK HOUSE IDENTITY 8 RECORD SPEECH see figure 4 1a USER 5 NAME NEXT USER 6 NAME NEXT USER 7 NAME NEXT USER 8 NAME RECORDING ENDED TALK NOW RECORD A M...

Страница 22: ...m does not recognize your installer code this indicates you must have programmed a user code that is identical with your installer code If so access the user menu and change the code that is identical...

Страница 23: ...roper function of all detectors in the system a comprehensive diagnostic test is required To perform this test refer to figure 4 9 5 3 Keyfob Transmitter Test Initiate transmission from each transmitt...

Страница 24: ...tery pack correct insertion and tightened battery compartment lid the TROUBLE indicator should extinguish However the MEMORY message will now blink in the display caused by the tamper alarm you trigge...

Страница 25: ...12 Flood 13 Interior Zone Locations Note down the intended location for each detector When programming you may select one of 26 available zone names plus 5 custom zone names that you can add see Figur...

Страница 26: ...ist Tx Transmitter Type Enrolled to Zone Name of holder Assignment 1 2 3 4 5 6 7 8 9 10 APPENDIX B X 10 Unit and PGM Output Assignments Unit Controlled ON ON ON ON ON ON ON by Timer ON by Zone No ON N...

Страница 27: ...od alarm restore FT Fire Detector Clean XR Sensor Battery Restore FJ Fire detector trouble XT Sensor Battery Trouble FR Fire Restore YR System Battery Restore GA Gas alarm YT System Battery Trouble Di...

Страница 28: ...ou choose to mute them Exit Delay The exit delay begins once the user arms the system It allows him to leave via interior zones and a doorway before arming actually takes effect When the exit delay st...

Страница 29: ...nd anti tamper protection They therefore trigger an alarm in both armed and disarmed states 24 Hour Zone Silent Upon detection this zone initiates a silent alarm meaning that the sirens do not functio...

Страница 30: ...and HOME together for 2 sec initiates PANIC alarm Pressing AWAY for 2 sec initiates Latchkey arming DISARM AWAY AUX HOME MCT 234 B MCT 231 201 N A in North America Single button pendant units The MCT...

Страница 31: ...e to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 0 To be certain of the number of devices that may be connected to the line as determined by the total RENs...

Отзывы: