ABBRA INSTALLATION GUIDE Version.04 4/12/17 

19 

4.6.4  GSM Line Failure Reporting 

Here  you  determine  whether  GSM  network  failure  will  be 
reported after 2 min., after 5 minutes, after 15 min., or after 
30 minutes. 
Available  options: 

don't report

2 min

5 min

15 min

, or 

30 min

4.6.5  GSM Line Purpose 

Define whether the GSM unit will serve as a backup for the 
regular  telephone  line,  as  a  primary  communication 
channel  or  as  the  only  telephone  channel  or  for  sending 
SMS only. 
Available options are: 

GSM is backup, GSM is primary

 or 

GSM only 

or 

SMS only

.

 

 

4.7 DEFINING OUTPUT PARAMETERS 

4.7.1 Preliminary Guidance 

This mode allows you: 

a. Events/conditions  selection  under  which  the  PGM 

(programmable)  output  and  fifteen  “X-10”  devices  will 
function.  

b. Function type selection for every X-10 unit and  for PGM 

output. 

c.  General definitions selection for X-10 units 

d. Selection of the internal siren or STROBE light (that will 

be activated according to system programming). 

e. Enrolling 2-way X-10 units. 

The  process  is  shown  in  Fig.  4.7.  Each  selected  option is 
displayed  with  a  dark  box  at  the  right  side.  To  review  the 
options,  repeatedly  press  <Next>  or  <Back>  button,  until 
the  desired  option  is  displayed,  then  press  <View/Select> 
button. 

 

4.7.2 Define PGM  

For the PGM output, you can select 

disable, turn on

turn 

off

 or 

pulse active

 (turn on for predefined period, selected 

by 

PULSE TIME

), as follows:   

n

 

BY ARM AWAY (

upon AWAY arming). 

n

 

BY ARM HOME

 (upon HOME arming). 

n

 

BY DISARM

 (upon disarming). 

n

 

BY MEMORY

 (activated upon registration of an alarm in 

the memory, turned off upon memory clearing). 

n

 

BY DELAY

 (during exit / entry delays). 

n

 

BY  KEYFOB

  (upon  AUX  button  pressing  in  the keyfob 

transmitter  /  MCM-140+,  if  “

PGM/X-10

”  is  selected  in 

“Define Panel” menu, location 17).  

n

 

BY ZONES 

(by disturbance in each of 3 selected zones, 

irrespective of arming / disarming). If you select 

toggle

the PGM output will be turned on upon event occurrence 
in  these  zones  and  will  be  turned  off  upon  next  event 
occurrence, alternately.  

n

 

BY  LINE  FAIL:

  PGM  output  is  ON  if  telephone  line  is 

disconnected. 

4.7.3 Defining INT/STRB 

Here  you  determine  if  the  INT  output  will  be  used  for  an 

internal siren

 or for a 

strobe

4.7.4 X-10 GENERAL DEF 

(Not evaluated by UL) 
For X-10 devices, you can select the following actions: 

n

  FLASH ON ALARM

 (you can select 

no flash

 or 

all light 

flash

,  to  control  X-10  lighting  devices  in  alarm 

conditions). 

n

 

TRBL  INDICATION 

(you  can  select 

don't  indicate

  or 

indicate

  for  X-10  failure  indication  by  the  TROUBLE 

LED). 

n

 

FAIL  REPORT 

(You  can  select 

report  to  central 

station 1

report to central station 2, report to pager, 

report  to  private  telephone

  and 

send  SMS

,  for  X-10 

devices failure reporting). 

n

 

3 PHASES & FREQ

 (you can select 

disable 3 phase

phase  50  Hz

,  or 

3  phase  60  Hz

  to  define  the  X-10 

signal transmission type). 

n

 

LOCKOUT TIME

 (You can enter daytime limits between 

which X-10 lighting devices controlled by sensors will be 
off, even when the associated sensors are triggered). 

In UL installations, this function shall not be used.

 

4.7.5 X-10 UNIT DEFINE 

(Not evaluated by UL) 

For  the  fifteen  X-10  units  you  can  perform  the  following 
programming actions: 
a. House code selection (a code letter from A to P that will 

distinguish the site in which the system is installed from 
other sites in the neighborhood). 

b. Specific number definition for every X-10 unit (01 – 15). 
c.  Enrolling 1-way X-10 units 
d.  Enrolling 2-way X-10 units (that can perform status reporting). 

Note:

 If a 2-way X-10 unit is installed without enrolling, 

interference  to  the  1-way  X-10  units  operation  may 
occur. 

e. For each X-10 unit you can select 

disable, turn on

turn 

off

  or 

pulse  active

  (turn  on  for  predefined  period, 

selected  by 

PULSE  TIME

),  upon  the  following 

conditions:  

n

 

BY ARM AWAY (

upon AWAY arming). 

n

 

BY ARM HOME

 (upon HOME arming). 

n

 

BY DISARM

 (upon disarming). 

n

 

BY MEMORY

 (activated upon registration of an alarm 

in the memory, turned off upon memory clearing). 

n

 

BY DELAY

 (during exit / entry delays). 

n

 

BY  KEYFOB

  (upon  AUX  button  pressing  in  the 

keyfob  transmitter  /  MCM-140+,  if  “

PGM/X-10

”  is 

selected in “Define Panel” menu, location 17).  

n

 

BY  ZONES 

(by  disturbance  in  each  of  3  selected 

zones,  irrespective  of  arming  /  disarming).  If  you 
select 

toggle

, the PGM output will be turned on upon 

event occurrence in these zones and will be turned off 
upon next event occurrence, alternately.  

Содержание Fully Supervised Wireless Alarm Control...

Страница 1: ...liminary Guidance 11 4 4 2 Entry Delays 1 2 11 4 4 3 Exit Delay 11 4 4 4 Bell Time 11 4 4 5 Abort Time 11 4 4 6 Alarm Cancel 11 4 4 7 Quick Arm 12 4 4 8 Bypass 12 4 4 9 Exit Mode 12 4 4 10 Piezo Beeps...

Страница 2: ...o the master user after testing the system Appendices A 1 and A 2 will help you prepare an installation plan Please take time to fill out the forms your job will become much easier and confusion will...

Страница 3: ...m in accordance with zone attributes Siren Signals Continuous intrusion 24 hours panic triple pulse pause triple pulse fire Siren bell Timeout Programmable 4 min by default Internal Sounder Output At...

Страница 4: ...to Pager PIN No Alarm Type Zone No 2 5 Physical Properties Operating Temp Range 32 F to 120 F 0 C to 49 C Storage Temp Range 4 F to 140 F 20 C to 60 C Humidity 85 relative humidity 30 C 86 F Size 10...

Страница 5: ...NSTALLATION GUIDE Version 04 4 12 17 5 Figure 3 1 Backup Battery Installation Open cover 1 Keypad cover 2 Remove screw and open battery compatment Remove screw to release wall mount bracket Connect ba...

Страница 6: ...6 ABBRA INSTALLATION Figure 3 2 Mounting the Control Panel...

Страница 7: ...ries has simple phone X 10 and AC power jacks pre installed No power or phone wiring is required simply plug the AC power cord into the AC power jack the phone cord into the telephone jack and the X 1...

Страница 8: ...1 3 8 Connecting Abbra to Computer The control panel can be equipped with an optional RS232 module for serial data interchange with a local computer If this module is not supplied a special plastic c...

Страница 9: ...reless siren Before beginning gather all the devices that you intend to enroll and make sure they all have batteries installed Your control panel must recognize the unique identification code ID of ea...

Страница 10: ...rolling action NEXT OK ENROL WL SIREN NEXT WL siren No 1 or 2 e g 2 SIREN No siren No 2 siren No 2 OK OK OFF TO DELETE Momentarily press the wireless siren self test button until a squawk is heard 1 s...

Страница 11: ...lumns even before you start and proceed to program according to your own list Remember A delay zone is also a perimeter zone by definition Zone types are fully explained in Appendix D For UL installat...

Страница 12: ...ing which the beeping rate increases Locations No 1 entry delay 1 and 2 entry delay 2 allow you to program the length of these delays Available options for each delay are 00s 15s 30s 45s 60s 3m and 4m...

Страница 13: ...rs after having been bypassed if the system remains armed The available options are shut after 1 shut after 2 shut after 3 and no shutdown In UL installations No Shutdown must be selected 4 4 14 Cross...

Страница 14: ...ted The available options are enable and disable 4 4 28 Disarm Option fig 4 4 location 28 Here you determine when it is possible to disarm the system A Any time B During entry delay by using the Abbra...

Страница 15: ...entry dly1 30 s entry dly1 45 s entry dly1 60 s entry dly1 3 m entry dly1 4 m abort time 00 s abort time 15 s abort time 30 s abort time 45 s abort time 60 s abort time 2 m abort time 3 m restart exit...

Страница 16: ...its 5 seconds F 5 Not applicable in phone numbers To enter a series of digits use the following keys Numeric keypad to enter the number Next Item moves the cursor from left to right Back moves the cur...

Страница 17: ...he pager s address The paging company s computer needs this input for routing messages to the specific pager The PIN sequence precedes any digital message that the Abbra sends to the pager to report a...

Страница 18: ...talled or not installed Available options are installed or not installed 4 6 2 1st 2nd 3rd 4th SMS Number Here you define the first second third and fourth SMS phone number including area code 16 digi...

Страница 19: ...3 Defining INT STRB Here you determine if the INT output will be used for an internal siren or for a strobe 4 7 4 X 10 GENERAL DEF Not evaluated by UL For X 10 devices you can select the following act...

Страница 20: ...PGM NEXT PGM NEXT Dxx BY ARM AWAY Dxx BY ARM HOME Dxx BY MEMORY OK ONE WAY UNIT PLEASE WAIT test fail test OK NEXT TWO WAY UNIT OK OK OK OK to Enroll enroll OK Enroll FAIL enroll fail HOME Exit X 10...

Страница 21: ...e fig 4 3 The recording process is shown below NEXT OK HOUSE IDENTITY 8 RECORD SPEECH see figure 4 1a USER 5 NAME NEXT USER 6 NAME NEXT USER 7 NAME NEXT USER 8 NAME RECORDING ENDED TALK NOW RECORD A M...

Страница 22: ...m does not recognize your installer code this indicates you must have programmed a user code that is identical with your installer code If so access the user menu and change the code that is identical...

Страница 23: ...roper function of all detectors in the system a comprehensive diagnostic test is required To perform this test refer to figure 4 9 5 3 Keyfob Transmitter Test Initiate transmission from each transmitt...

Страница 24: ...tery pack correct insertion and tightened battery compartment lid the TROUBLE indicator should extinguish However the MEMORY message will now blink in the display caused by the tamper alarm you trigge...

Страница 25: ...12 Flood 13 Interior Zone Locations Note down the intended location for each detector When programming you may select one of 26 available zone names plus 5 custom zone names that you can add see Figur...

Страница 26: ...ist Tx Transmitter Type Enrolled to Zone Name of holder Assignment 1 2 3 4 5 6 7 8 9 10 APPENDIX B X 10 Unit and PGM Output Assignments Unit Controlled ON ON ON ON ON ON ON by Timer ON by Zone No ON N...

Страница 27: ...od alarm restore FT Fire Detector Clean XR Sensor Battery Restore FJ Fire detector trouble XT Sensor Battery Trouble FR Fire Restore YR System Battery Restore GA Gas alarm YT System Battery Trouble Di...

Страница 28: ...ou choose to mute them Exit Delay The exit delay begins once the user arms the system It allows him to leave via interior zones and a doorway before arming actually takes effect When the exit delay st...

Страница 29: ...nd anti tamper protection They therefore trigger an alarm in both armed and disarmed states 24 Hour Zone Silent Upon detection this zone initiates a silent alarm meaning that the sirens do not functio...

Страница 30: ...and HOME together for 2 sec initiates PANIC alarm Pressing AWAY for 2 sec initiates Latchkey arming DISARM AWAY AUX HOME MCT 234 B MCT 231 201 N A in North America Single button pendant units The MCT...

Страница 31: ...e to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 0 To be certain of the number of devices that may be connected to the line as determined by the total RENs...

Отзывы: