1YSA160045-EN - Rev. 5
13 / 33
C.4.4.4.3.
Scenario_2: Three-Phase tripping operation without handshake request
Configure the wiAutoLink as well in chapter 4.4.1.2, but here in this example the “Allowed partial trip” flag is enabled.
Hence, in the normal condition, the LED flashing every 10s.
When the counting overload condition has been reached, the tripping operation will be followed on all three-phase apparatus if the
intercommunication procedure between the devices succeeded, or will trip on the apparatus, which detected the fault, eventually.
To download parameters into wiAutolink, please refer to the configuration wizard instruction section:
Network Pin: 1234
Pickup Current: 60A.
Inrush threshold: 40%
Device Type: Three phase.
Frequency Setting: 50 Hz.
Reset Time: 30 s.
Count settings: 2.
Zero Current Threshold: 200 mA
Enable Status LED: yes
Allow partial trip: yes
C.4.4.4.4.
Scenario_3: Single-Phase tripping operation with blinking led active
Configure the wiAutoLink in single-phase, and but here in this example the “enable Status LED” is enabled.
Hence, in the normal condition, the LED flashing every 10s.
When the counting overload condition has been reached, the tripping operation will be followed in single-phase apparatus.
Hence, the “Allowed partial trip” do no have effect because in single phase configuration.
To download parameters into wiAutolink, please refer to the configuration wizard instruction section:
Network Pin: 1234
Pickup Current: 60A.
Inrush threshold: 40%
Device Type: Single phase.
Frequency Setting: 50 Hz.
Reset Time: 30 s.
Count settings: 2.
Zero Current Threshold: 200 mA
Enable Status LED: yes
Allow partial trip: yes or not (do not have effect in single phase)
C.4.4.4.5.
Scenario_4: Single-Phase tripping operation with blinking led Disabled
Configure the wiAutoLink as well in chapter 4.4.1.4, but here in this example the, and but here in this example the “enable Status
LED” is disabled.
Hence, in the normal condition, the LED flashing only once time during the start-up of the device.
When the counting overload condition has been reached, the tripping operation will be followed in single-phase apparatus.
Hence, the “Allowed partial trip” do no have effect because in single phase configuration.
To download parameters into wiAutolink, please refer to the configuration wizard instruction section:
Network Pin: 1234
Pickup Current: 60A.
Inrush threshold: 40%
Device Type: Single phase.
Frequency Setting: 50 Hz.
Reset Time: 30 s.
Count settings: 2.
Zero Current Threshold: 200 mA
Enable Status LED: yes