1
) For further details on the cell type assignments see the section on dimensions for circuit breaker on withdrawable assembly.
(
2
) At operating voltages lower than the rated voltage, the same values fundamentally apply as for the rated voltage. Higher values on request.
(
3
) With a motorized withdrawable part, the weight is increased by approx. 2 kg
M ED I U M VO LTAG E P R O D U C T S
37
10.3 Technical data
Circuit breakers on withdrawable part (
1
)
10.3.1 Performance data and weights
Rated voltage
kV
12
17.5
24
Rated frequency
Hz
50/60
50/60
50/60
Rated lightning impulse withstand voltage
kV
75
95
125
Rated power frequency withstand voltage
kV
28
38
50
Rated of rise of transient recovery voltage
kV/μs
0.34
0.42
0.47
Peak transient recovery voltage
kV
20.6
30
41
Rated operating sequence
O-3 min-CO-3 min-CO
Rated operating sequence for autoreclosing
O-0.3 s-CO-3 min-CO
Guideline values for function times:
Closing time
approx. 16 ms
Opening time
approx. 10 ms
Arcing duration (at 50 Hz)
≤ 15 ms
Total opening time
≤ 25 ms
Minimum command time on closing
2 ms
Minimum command time on opening
2 ms
Breaker
type
Rated
voltage
Rated
current
Rated
short-
circuit
breaking
current
symm. (
2
)
Short-
circuit
breaking
current
asymm. (
2
)
Rated
short-
circuit
making
current
(peak) (
2
)
Rated
short-
circuit
duration
Pole
centres (
1
)
Weight
(
2
) (
1
) (
3
)
Permissible
of vacuum-
interrupter
switching
operations
VM1-T
kV
A
kA
kA
kA
s
mm
approx.
kg
Figure 9/28
page 31/32
1212-16
12
1250
16
150
131
Diagram A
1212-20
1250
20
150
131
Diagram B
1216-20
1600
210
135/140
Diagram C
1206-25
630
25
27.3
63
3
150
127
Diagram D
1212-25
1250
150
131
Diagram D
1216-25
1600
210
135/140
Diagram E
1220-25
2000
210
135/140
Diagram E
2412-20
24
1250
20
210
142/1407
Diagram B