36.3
36.4
?
36.2
/ A: 24 V ...48 V AC/DC; 60 V DC
LOGIC
3
4
27
2
-Q0
15
10
16
26
30
-RL1
-MO2
-MO1
-MC
-DN
-DR
-DC1
-DC2
-DO1
-DO2
-BB4
-MU
B: 100 V AC; 1 10 V ...240 V AC/DC
=
=
-MS
VM1-T
- VACUUM CIRCUIT BREAKER
24
—
9. Figures
Sample for coding
Control
Code
B1
B2
B3
B4
B5
B6
wiring
Pin
X
X
socket
Hole
Control
Hole
X
X
wiring
Pin
plug
Code
B1
B2
B3
B4
B5*
B6
• B5 is used in spec ial cases only
Figure 9/14: Possible encoding of the control wiring plug connector,
58-way control wiring socket.
36.2 Control wiring socket
36.3 Centres for coding pins and bores
36.4 Bore for the actuating pin on the control wiring plug
for controling the auxiliary switch.
Coding:
( ... ) In brackets is stated
the corresponding coding
designation for the
control wiring plug (1 0.2)
The coding pins can
befitted in the
control wiring socket (1 0.1)
and/or in the
control wiring plug. (10.2)
Basic design:
Number of sockets optional,
but always with the
basic assignment:
1,8, 10, 20, 21, 31, 33, 40.
Sockets and pins can be
mixed In the control wiring
socket (1 0.1) and control
wiring plug (1 0.2) as required
Figure 9/13: Block diagram of the magnetic actuator mechanism.
2
”READY” lamp (LED)
3
ON push-button
4
OFF push-button
10
Actuator
15
Sensor for “circuit breaker OFF” signal
16
Sensor for “circuit breaker ON” signal
26
Storage capacitor
27
Circuit breaker control unit
30 Converter for operation with AC or DC voltage
-Q0 Circuit breaker
External circuit breaker connection:
Inputs:
-MU
Switching command OFF (closed circuit)
-RL1
Closing lock-out (closed circuit)
-MO2
Switching command OFF 2 (open circuit)
-MO1
Switching command OFF 1 (open circuit)
-MC
Switching command ON (open circuit)
-MS
Supply voltage
Outputs:
-BB4
Fleeting contact (100 ms)
-DN
NOT READY (NCC)
-DR
READY (NOC)
-DC2
ON signal 2 (NOC)
-DO2
OFF signal 2 (NOC)
-DC1
ON signal 1 (NOC)
-DO1
OFF signal 1 (NOC)
See page 42 for comparison of IEC/VDE designations.