VM1-T
- VACUUM CIRCUIT BREAKER
30
—
10. Technical data
10.1 Technical data, general
10.1.1 Technical data Control electronics
a) Binary inputs
The following applies to all 5 input channels:
•
Electrical isolation between all inputs and from
the electronics: 2.0 kV AC
•
AC/DC operation (any polarity for DC)
•
Response range at inputs -MO1, -MC und -MO2,
according to the type of filter card 1):
- 24 V
–15%
… 60 V
+15%
AC
24 V
–30%
… 60 V
+15%
DC
- 100 V
–15%
… 125 V
+15%
AC
100 V
–30%
… 125 V
+15%
DC
- 220 V
–15%
… 240 V
+15%
AC
220 V
–30%
… 240 V
+15%
DC
•
Response range -MU
2
) adjustable, see page 26
•
Response range -RL1:
- 24 V
–15%
… 240 V
+15%
AC
- 24 V
–30%
… 240 V
+15%
DC
•
Base load at input:
- 300 kΩ (-MU
2
), -RL1, -MO
2
)
3
)
- 14 kΩ (-MO1, -MC)
•
Inputs protected from voltage surges.
b) Binary outputs
The following applies to all 5 output channels:
•
Electrical isolation between all outputs and
from the electronics: 2.0 kV AC
•
Switching voltage: max. 400 V AC or 300 V DC
•
Switching current: max. 6 A / 250 V AC
(resistive)
• ON resistance: 100 mΩ
•
Switch putputs: NOC, NCC and fleeting contact
•
Duration of fleeting contact pulse: 100 ms
•
Output connections: varistors
(
1
) Different response ranges for individual inputs on request.
(
2
) Full version on the control module
(
3
) In general, with AC signals which are connected via long lines, it should
be checked whether the installed base load of 300 kΩ is sufficient
(mutual capacitive coupling!) to ensure a reliably low interference level.
Otherwise, an appropriately dimensioned resistor or capacitor is to be
connected in parallel at the input terminals.
10.1.2 Technical data
AC/DC converter
•
Input voltage ranges, optional:
- Power pack A:
- 24 V
–15%
… 48 V
+15%
AC
- 24 V
–15%
… 60 V
+15%
DC
- Power pack B:
- 100 V
–15%
… 240 V
+10%
AC
- 110 V
–15%
… 240 V
+10%
DC
•
Protection of power feed (must be ordered):
- Power pack A:
ABB-Stotz m.c.b.: S 282 UC-K; 1.6 A
- Power pack B:
ABB-Stotz m.c.b.: S 282 UC-K; 1.0 A
•
Power consumption on the input side during a
charging process: ca. 100 W
•
Power consumption in normal position: P < 10 W
•
Charging times of the capacitor (example for DC
voltage):
- a) Initial charging on commissioning:
- Breakers up to 25 kA: max. 20s depending on
the supply voltage.
In this time, the capacitor(s) is/are charged to
80 V, and an ON-OFF operating cycle is
already possible at 69 V. (The ”READY” lamp
indicates readiness for switching. A flashing
“READY” lamp signals recharging of the
capacitor. Switching readiness is enabled
during that time).
- b) Recharging after a switch operation to a
charge of 80 V: max. 10s
Содержание VM1-T
Страница 43: ...MEDIUM VOLTAGE PRODUCTS 43 ...