8
Figure 2/1: VD4 circuit-breaker for fixed installation,
12 kV, 1250 A, mechanism side
1)
Approximate values
2)
At rated supply voltage
Figure 2/2: VD4 circuit-breaker for fixed installation,
12 kV, 1250 A, pole side
2.3
Technical data
Motor-operated mechanisms
Groschopp-Motor
Rated
Power
Motor protection
Charging
supply
consumpt-
(ABB-Stotz m.c.b.)
time
voltage
ion
1)
(maxi
-
mum)
2)
V
VA/W
A
s
AC
110
260
1.6 S 281UC-K
10
220
260
0.75
10
240
260
0.75
10
DC
60
240
3.0 S 282UC-K
10
110
230
1.6
10
125
260
1.6
10
220
240
0.75
10
240
260
0.75
10
Gefeg-Motor
Rated
Power
Motor protection
Charging
supply
consumpt-
(ABB-Stotz m.c.b.)
time
voltage
ion
1)
(maxi
-
mum)
2)
V
VA/W
A
s
AC
110
150
1.6 S 281UC-K
15
220
150
0.75
15
240
170
0.75
15
DC
24
130
4.0 S 282UC-K
15
48
130
3.0
15
60
130
2.0
15
110
140
1.0
15
125
160
1.0
15
220
140
0.75
15
240
150
0.75
15