- 92 -
000693DG
5 - Installation
• Once the phase of mechanical installation of the METER is finished,
it is necessary to configure the METER in order to make it compatible
with the inverter. Set the parameters on the meter display as set out in
the table:
Parameter
Settings
Address
1
Protocol
MODBUS
Baud rate
19200
Parity
EVEN
The settings are made by using the keypad and the display on the meter:
1. Press for two seconds to access the setup menu of the meter.
2. Press repeatedly
until the display shows “
Set
”.
- Press
to confirm.
3. Press repeatedly
until the display shows “
RS-485
”.
- Press
to confirm.
4. Press repeatedly
until the display shows “
Prot
”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly
until the display shows “
Modbus
”.
- Press
to confirm the change.
- Press for two seconds to return to the RS485 menu.
5. Press repeatedly
until the display shows “
Baud
”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly and select 19200.
- Press
to confirm the change.
- Press for two seconds to return to the RS485 menu.
6. Press repeatedly
until the display shows “
Address
”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly and select 1.
- Press
to confirm the change.
- Press for two seconds to return to the RS485 menu.
7. Press repeatedly
until the display shows “
Parity
”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly and select even.
- Press
to confirm the change.