![background image](http://html1.mh-extra.com/html/abb/tzidc-200/tzidc-200_commissioning-instructions_3459559032.webp)
Ex relevant specifications
30 - EN
TZIDC-200, TZIDC-210, TZIDC-220 CI/TZIDC-200/210/220-EN
IECEx
Ex ia IIC T6
Type-Examination Test
Certificate:
IECEx TUN 04.0015X, Issue no.:
0
Type:
Intrinsically safe
Temperature class:
T4, T5, T6
Permissible ambient temperature:
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 55 °C
T6: -40 °C < T
amb
< 40 °C
Signal circuit for PROFIBUS PA only for connecting a certified
intrinsically safe circuit (e.g., FISCO power supply or barriers) with
max. values acc. to:
FISCO power
supply ia/ib
for Grp. IIB/IIC
FISCO power
supply ia/ib
for Grp. IIB/IIC
Barriers or
power supply
ia/ib for Grp.
IIB/IIC
Voltage
Ui = 17.5 V
Ui = 17.5 V
Ui = 24 V
Current
li = 380 mA
li = 360 mA
li = 250 mA
Power
Pi = 5.32 W
Pi = 2.52 W
Pi = 1.2 W
Characteri
stic
rectangular trapezoidal Linear
7.3
TZIDC-220
FM Approval HLC 7/04 3019164
Explosion proof; enclosure 4X; T5, max. 82 °C
CL I; Div 1; Grp. C-D
Dust ignition-proof; enclosure 4X; T5; max. 82 °C
CL II, III, Div 1 Grp. E-F-G
CSA Certification 1555690
Explosion proof; enclosure 4X
Temperature range: -40 … 85 °C
T5, max. 85 °C ; T6, max. 70 °C
CL I; Div 1; Grp. C-D
CL II; Div 1; Grp. E-F-G
CL III
ATEX / GOST Ukraine
II 2G EEx d II C T4/T5/T6
Type-Examination Test
Certificate:
DMT 02 ATEX E 029 X
Type:
Flameproof enclosure for
equipment
Device class:
II 2G (EEx ib IIC)
Temperature class:
T4, T5, T6
Permissible ambient
temperature:
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 80 °C
T6: -40 °C < T
amb
< 65 °C
ATEX
II 2G EEx ia IIC T6
Prototype test certificate:
TÜV 02 ATEX 1831 X
Type:
Intrinsically safe equipment
Device class:
II 2G (EEx ia IIC)
Temperature class:
T4, T5, T6
Permissible ambient
temperature:
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 55 °C
T6: -40 °C < T
amb
< 40 °C
IECEx
Ex ia IIC T6
Prototype test certificate:
IECEx TUN 04.0015X, Issue no.: 0
Type:
Intrinsically safe
Temperature class:
T4, T5, T6
Permissible ambient
temperature:
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 55 °C
T6: -40 °C < T
amb
< 40 °C
Signal circuit for FOUNDATION fieldbus only for connecting a
certified intrinsically safe circuit (e.g., FISCO power supply or
barriers) with max. values acc. to:
FISCO power
supply ia/ib
for Grp. IIB/IIC
FISCO power
supply ia/ib
for Grp. IIB/IIC
Barriers or
power supply
ia/ib for Grp.
IIB/IIC
Voltage
Ui = 17.5 V
Ui = 17.5 V
Ui = 24 V
Current
li = 380 mA
li = 360 mA
li = 250 mA
Power
Pi = 5.32 W
Pi = 2.52 W
Pi = 1.2 W
Characteri
stic
rectangular trapezoidal Linear
Change from one to two columns
Содержание TZIDC-200
Страница 2: ......
Страница 33: ...Ex relevant specifications CI TZIDC 200 210 220 EN TZIDC 200 TZIDC 210 TZIDC 220 EN 31...