![background image](http://html1.mh-extra.com/html/abb/tzidc-200/tzidc-200_commissioning-instructions_3459559027.webp)
Commissioning
CI/TZIDC-200/210/220-EN TZIDC-200, TZIDC-210, TZIDC-220
EN - 25
6.2
TZIDC-210 / TZIDC-220
bieten
1.
Feed in pneumatic auxiliary power
2.
Connect the bus to the bus terminals with any polarity (or auxiliary power 9 ... 32 V DC),
mA
%
C
°
is displayed
3.
Check mount:
• Press and hold down
and
. On completion of the countdown from 3 to 0,
release
and
. The unit switches to the operating level, mode 1.x
• Press and hold down
and
• Additionally,
press or until operating mode 1.3 (manual adjustment within the sensor
range) is displayed. Release
• Press or to move the actuator into the mechanical end position. Check the end
positions. The rotation angle is displayed in degrees. For high-speed mode, press and
simultaneously.
Recommended range:
- between -28 ... 28° for linear actuators
- between -57 ... 57° for rotary actuators
Minimum angle: 25°
4.
Go back to the bus level:
• Press and hold down
and
. On completion of the countdown from 3 to 0,
release
and
,
mA
%
C
°
is displayed.
5.
Run Autoadjust.
• Check that the unit is on the bus level ("REMOTE")
For linear actuators
1)
:
• Press and hold down
until
is displayed. Release the control button
• Press
again and hold down until the countdown ends
• Release
. This starts Autoadjust
For rotary actuators
1)
:
•
Press and hold down
until
is displayed. Release the control button
•
Press
again and hold down until the countdown ends
•
Release
. This starts Autoadjust