Operating instruction manual
| TX Thermal Disperson Level Switches 21
12.0 APPENDIX C - Remote Mounting
TERMINAL NUMBER
1
2
3
4
5
HTR
HTR
ACT
COM
REF
Standard Temperature
Range
RED
RED
YEL
BLK
GRN
Special Temperature
Range, Option H1 –320°F
- +500°F
RED
RED
WHT
BLK
GRN
SEE WIRE MARKERS
Special Temperature
Range, Option H2 –100°F
- +900°F
TERMINAL NUMBER
1
2
3
4
5
HTR
HTR
ACT
COM
REF
Integral Electronics
RED
RED
YEL
BLK
GRN
Remote Electronics Type J
Cable (PVC)
BLUE
WHITE + DRAIN
WHT
BLK
GRN
Remote Electronics Type F
Cable (Teflon)
RED OF PAIR 1
RED FOIL
BLACK OF PAIR
1 + DRAIN OF
PAIR 3
WHITE OF PAIR
2 GRN FOIL
BLACKS OF
PAIRS 2 & 3
GREEN
OF PAIR
3 BLUE
FOIL