![ABB TTH300 Series Скачать руководство пользователя страница 65](http://html.mh-extra.com/html/abb/tth300-series/tth300-series_operating-instruction_5294065.webp)
TTH300
HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G
65
Factory settings
Firmware settings
The transmitter is configured ex works.
HART® devices from SW-Rev. 3.00
These devices can be reset to the factory setting, as well as to the setting according to the customer order.
With the menu item “Factory reset” in the service menu, the factory settings are reset to the factory settings according to the
following table (corresponds to standard configuration BS).
The menu item “Reset to Order” in the service menu is used to reset to the configuration ordered by the customer (default
configuration BS, customer-specific configuration without special user characteristic BF or customer-specific configuration with
special user characteristic BG).
The currently set HART protocol remains unchanged during a factory reset and a reset to order.
Devices with PROFIBUS PA®, FOUNDATION Fieldbus® and HART® (all SW revisions)
The following table with the corresponding parameter values applies.
Menu
Designation
Parameter
Factory setting
Device Setup
Write protection
–
No
Input Sensor 1
Sensor Type
Pt100 (IEC60751)
R-Connection
Three-wire
Measured Range Begin
1
0
Measured Range End
1
100
Engeneering Unit
Degrees °C
Damping
Off
Process Alarm
Fault signaling
1
To SW-Rev. 1.03: Overrange / high alarm 22 mA
1
From SW-Rev. 3:00: Underrange / low alarm
3.5 mA
1
Input Sensor 2
Sensor Type
Off
Input / output assignment
Measurement type
Sensor 1
TAG
–
–
HART Descriptor
1
–
To SW-Rev. 1.03: TIXXX-
1
Display
Display Value
–
Process Variable
Bargraph
1
–
Yes, output %
1
Language
–
English
Contrast
–
50 %
Communication
HART Burstmode
1
Status
1)
Off
1
Bus Address
2 3
–
126
2
/ 30
3
Simulation mode
3
–
Off
3
HART Protocol
–
HART 5 / 7
4
1 Only applies to HART transmitters
2 Only applies to PROFIBUS PA transmitters
3 Only applies to FOUNDATION Fieldbus transmitters
4 The currently set HART protocol remains unchanged during any type of reset (all SW revisions).