![ABB TTH300 Series Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/abb/tth300-series/tth300-series_operating-instruction_5294019.webp)
TTH300
HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G
19
6
Transport and storage
Inspection
Check the devices immediately after unpacking for possible
damage that may have occurred from improper transport.
Details of any damage that has occurred in transit must be
recorded on the transport documents.
All claims for damages must be submitted to the shipper
without delay and before installation.
Transporting the device
Observe the following instructions:
• Do not expose the device to humidity during transport.
Pack the device accordingly.
• Pack the device so that it is protected against vibrations
during transport, for example, by using air-cushioned
packing.
Storing the device
Bear the following points in mind when storing devices:
• Store the device in its original packaging in a dry and
dust-free location.
• Observe the permitted ambient conditions for transport
and storage.
• Avoid storing the device in direct sunlight.
• In principle, the devices may be stored for an unlimited
period. However, the warranty conditions stipulated in
the order confirmation of the supplier apply.
Ambient conditions
The ambient conditions for the transport and storage of the
device correspond to the ambient conditions for operation of
the device.
Adhere to the device data sheet!
Returning devices
For the return of devices, follow the instructions in
Repair
on
page 72.
7
Installation
DANGER
Improper installation and commissioning of the device
carries a risk of explosion.
For use in potentially explosive atmospheres, observe the
information in
Use in potentially explosive atmospheres in
accordance with ATEX and IECEx
on page 7 and
Use in
potentially explosive atmospheres in accordance with FM
and CSA
on page 13!
Ambient conditions
Ambient temperature
•
Default: −40
to 85
°C (−40
to 185 °F)
•
Optional: −50
to 85
°C (−58
to 185 °F)
• Restricted range during operation with LCD-indicator:
−20
to 70
°C (−4
to 158 °F)
• Restricted range during operation with explosion-proof
design: see corresponding certificate
Transport- / Storage temperature
−
50 to 85
°C (−58
to 185 °F)
Climate class in accordance with DIN EN 60654-1
Cx −40
to 85
°C (−40
to 185 °F) at 5 to 95 % relative air humidity
Max. permissible humidity in accordance with
IEC 60068-2-30
100 % relative air humidity
Vibration resistance in accordance with IEC 60068-2-6
10 to 2000 Hz at 5 g, during operation and transport
Shock resistance in accordance with IEC 60068-2-27
gn = 30, during operation and transport
IP rating
• Power supply circuit: IP 20
• Measurement current circuit: IP 00 or IP-rating of installation
housing