TTH300
HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G
57
Menu: Calibrate
Menu / parameter
Description
… / Calibrate
Measured range
Select the ‘
Measured range
’ submenu.
Analog Out
Select the ‘
Analog Out
’ submenu.
… / Calibrate / Measured range
Apply Lower Range
The current reading (PV) is used as the lower range limit (4 mA).
Apply Upper Range
The current reading (PV) is used as the upper range limit (20 mA).
… / Calibrate / Analog Out
Trim 4 mA
Adjusts the current output with a 4 mA setpoint
Value range: 3.500 to 4.500 mA
Trim 20 mA
Adjusts the current output with a 20 mA setpoint
Value range: 19.500 to 20.500 mA
Menu: Diagnosis
Menu / parameter
Description
… / Diagnosis
Looptest
Simulates the current output signal
Value range: 3.500 to 23.600 mA
0.000 mA: ends looptest
Device status
Diagnostic notice (maintenance required, failure, etc.)
SIL Check
Select the ‘SIL Check’ submenu.
Not passed: Use tool for a detailed check of the current device configuration.
Passed: SIL Configuration Check successful. The device configuration is valid for SIL Safety applications.
Temp. of Electronics
Select the ‘Temp. of Electronics’ submenu.
Drag indicator: maximum or minimum device temperature
Processvalue Sensor 1
Select the ‘Sensor 1 process data’ submenu.
Drag indicator: maximum or minimum sensor temperature for sensor 1
Reset: Resets the values
Processvalue Sensor 2
Select the ‘Sensor 2 process data’ submenu.
Drag indicator: maximum or minimum sensor temperature for sensor 2
Reset: Resets the values