29/72
TLE Series 625 to 1000 PurePulse™ UL S2
UPS Installation Guide / REV-B
4.7.3
Control cables interconnection
Note!
All the cables interconnection must be performed only by an ABB Service Technician!
TLE Series 625 & 750 - Control cables interconnection
Fig. 4.7.3-1 TLE Series 625 & 750 – Control cables interconnection
Pos.
Connection
From
Connecting to
1
XD1 – HAN Connector male (46 poles)
“Power Section” cabinet
“In/Out Section” cabinet
2
XD2 - HAN Connector male (32 poles)
“Power Section” cabinet
“In/Out Section” cabinet
Fig. 4.7.3-2 Connection of hearting connectors (HAN connectors)
Note! All these connections must be performed only by an ABB
Service Technician!
Proper dressing needs to be done for each cable assembly in
order to reduce the stress.
All the cables must be sufficiently (at least 4"/10cm) away from all
live parts.
Cable binders used to support the wiring must not be overly
tightened.
XD1
(46 poles)
XD2
(32 poles)
XD1
(46 poles)
XD2
(32 poles)
XD2 Connector (32 poles)
1
2
In/Out Section cabinet
Power Section cabinet
1
2
XD1 Connector (46 poles)
TLES_UL_625-750
_S2_UPS conne
ction cabinets_AB
B_03US