INSTALLATION INSTRUCTIONS

Important Note: A M6 torx screw driver or drive bit is required for the installation.

1.  Remove the unit from the packaging and inspect it for damage or imperfections. If any damage is found, do not install the unit and 

notify the Thomas & Betts Product Support Hotline in Australia on 1300 666 595.

2.  If all looks okay, proceed with the installation. Put the main frame upside down, remove six (6) special G6 x 1/2 counter sunk Torx 

screws by using a Torx pin driver or screw driver. Gently insert a small flat head screwdriver into the side of the front cover to lever 

it out, remove the front cover. See Figure 3.

3.  Loosen the thumb screws to remove the side diffusers. Leave the bottom diffuser on.

4.  Remove the Quickfit unit from the bracket by gently inserting a small screwdriver into the slot (at ‘D’ in Figure 4) on the front of the 

bracket towards the right hand end of the fitting to ease the locking tab into the fitting and away from the bracket. The unit is then 

free to slide to the right along the bracket for about 50mm, at which time the slots line up and it can be lowered away from the 

bracket, allowing the two to separate.

          Note: The main metal frame can be mounted on either side but inside can only be accessed from one end. Make sure to leave  

          a gap of at least 650mm to remove the Quickfit unit from the metal frame.

5.  Determine the mounting configuration and position, ie: Ceiling or Wall. Drill mounting holes at the positions as shown in Figure 1 or 

Figure 2. All drilling locations are indicated on the metal frame by dimple features. Due to the wide variety of building construction 

materials, mounting screws are not provided with the unit. Use appropriate hardware to suit the individual installation and structural 

support needs of the unit (17kg approx). The cable entry hole for Wall mounting can be drilled through the polycarbonate panel 

and the cable entry hole for ceiling mount must be drilled at the dimple at the centre of the top face, marked A as shown in                           

Figure 1. 

             

6.  Run the cables in the ceiling or wall space as appropriate through the cable hole into the bracket, a suitable bush may have to be 

used to protect the cable as it passes through the cable entry hole into the mounting bracket. Secure the main frame to the wall 

or ceiling before terminating any wiring. Strip, connect and terminate the cables as indicated in Figure 3. Ensure that the double 

insulation of the cable/s passes completely into the terminal block enclosure so that no single insulation is exposed when the cover 

is in place. Be careful with multi-strand conductors that all of the strands are twisted together before insertion into the terminal. 

Any stray strands that inadvertently come into contact with their neighbouring terminal or the metal frame of the fitting will cause 

undesirable results when the fitting is powered. Install the plastic panel over the terminal block.

Figure 3: Mains connection & how to get access to main frame

• 

Maintained  fittings  are  design  for  permanent  illumination:  Connect  incoming  unswitched  active,  neutral  and  earth  to  terminal 

marked USA, N and E respectively. 

• 

Data connection for Nexus LX product installation:

          The same colour wire from each data cables connects to the terminal .

          The other colour wire from each of the data cables connects to the terminal marked -.

          When connected, replace the terminal block cover so that it clicks and locks into place. 

• 

No mains or mains carrying cables are to be connected to the data terminals or cables.

7.  Fit the LED lamp (carefully follow the instruction label on top of the Quickfit unit) and attach the Quickfit unit to the mounting bracket 

by aligning the top left hand end of the unit (the end without the protruding electrical connecting metal lugs) with the large cut-away 

slot towards the left hand end of the bracket. Slip the left hand end of the unit up into the slot in the left hand end of the bracket 

(Step (1) in Figure 4) and hold the unit horizontal to and parallel with the bracket. It should be approximately 50mm to the right of 

its final destination. Simply slide the unit (Step (2) in Figure 4) 50mm to the left along and into the bracket to engage the connection 

and the locking tab. Once in place, the unit cannot be removed from the bracket without the use of a tool (a small screwdriver) to 

push in the locking tab at ‘D’ in Figure 4.

Figure 4: Quickfit Frame Insertion Diagram

8.  Once powered up, the LED lamp should energise and remain lit until the power supply fails. The emergency function of the 

light fitting should only operate when the normal lighting power supply fails or when somebody presses the manual test button 

located on the side of the unit. Normal status of the unit when powered, red LED indicates that the power is connected and the 

battery is charging or when commissioned on the Nexus LX/RF network and the unit is receiving a command from the Nexus LX/

RF controller to switch into emergency mode. Normal initial uncommissioned status of the indicating LED on the unit is flashing 

green. Once commissioned, the LED changes to a steady red and flashes red during test. Please refer to the Nexus LX/RF User 

& Technical Guide for a full detailed description of all possible LED states and their meanings.

9.  Check operation of the unit to ensure that the installation was successful. When powered up, allow a few minutes to give the battery 

a small charge, then press the manual test button located at the top right hand side edge of the unit. Hold the test button in for a 

few seconds and observe the operation of the lamp switching from mains to the emergency mode. If the lamp on emergency mode 

works momentarily, that’s okay. Try again in a few more minutes because if the battery was completely discharged, it may take a 

little time to charge up enough to operate even momentarily. After this time, press the test button again and if the lamp doesn’t work 

at all, check the supply, the connections and the trouble shooting guide at the end of this document.

10.  If the function test is successful, insert the side diffusers and tighten the thumbscrews by hand (clear polycarbonate panel must 

be facing outside). Check and adjust the gasket on the end cover, make sure it is sitting flush on the edge. Fit the end cover to the 

enclosure and secure it in place by six M6 Torx screws. For wall mount version you may not need screws on the that side.

REMOVAL INSTRUCTIONS

See steps 3 and 4 in the installation instruction.

TESTING PRECAUTIONS

Once the fitting is permanently connected to the mains supply, a commissioning discharge test as required in AS/NZS2293.2 must be 

carried out. You will need to allow 24 hours for the battery to fully charge prior to conducting this test, presently (at the time of writing), 

the standard requires that fittings operate in emergency mode for a period not less than 2 hours for their commissioning test and for 

not less than 90 minutes thereafter (it is required that 6 monthly discharge tests be carried out). You will need to keep the records for 

the commissioning test and enter them into the building emergency services logbook or via other recording methods as allowed by                 

AS/NZ2293.2.

CONSTRUCTION SITES

Continuously switching of the mains power supply that is connected to emergency light fittings during the construction phase of an 

installation will cause these fittings to discharge and charge their batteries many times over a short period; this can shorten the life of the 

battery and will also result in shortened emergency lamp life for fluorescent fittings. Thomas & Betts does not recommend such practices 

and may not honour the warranty on batteries when they are subjected to such harsh operating conditions. Emergency light fittings are 

designed to be discharge tested once every 6 months as per AS/NZS2293.2, subjecting the product to repeated discharge or charge 

cycles is regarded as an abuse of the fittings.

Insert here 

to remove

Cable Entry 

Holes

Terminal 

Block

Neutral Earth

Active

Side

A

100

500

407

500

Figure 1: Ceiling Mount

Figure 2: Wall Mount

Top