TROUBLE SHOOTING GUIDE
If you have installed and connected the unit as per the instructions listed earlier and it does not function correctly, use the following table
as a guide to fixing the problem. Look up the type of fault in the left column and check the possible causes from the right column.
If the unit still does not work after checking these possible causes, contact Thomas & Betts Service in Australia on 1300 666 595, Monday
to Friday, 8.30am to 4.30pm (AEST) and ask for help. Our trained service personnel will usually be able to take your call immediately and
assist you in resolving your difficulty. Thomas & Betts is committed to providing valuable Through-Life Support for its products.
Doc No: 29-99569
GREETINGS
Congratulations on choosing to use this Thomas & Betts product covered by our unique Through-Life Support system. This document is
designed to assist you during the installation of this product; for the safety of yourself and others
Thomas & Betts recommends
that you read this document thoroughly before commencing installation.
The fittings are designed for easy
installation. They are advanced pieces of electronic equipment which, when treated with care and maintained through regular and
appropriate servicing, will perform reliably for many years to come.
SAFETY WARNING
In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 Volt electrical installations.
Do not attempt to install or connect this product unless you are a licensed electrician.
Turn off and isolate the electrical supply before connecting this fitting to the building wires.
Do not touch the terminals of the terminal block when the light fitting is energised.
The only user-serviceable parts are fluorescent or halogen lamp/s. LED light sources are not user-servicable.
Do not tamper with the fitting or the warranty will be void.
As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS3000, AS/NZS2293).
Refer to the applicable standards for data and mains cabling installation procedures and requirements.
Important Note: This product is designed for indoor use only.
NEXUS LX (DATA CABLE SYSTEM)
The Nexus range of emergency light fitting are designed to be connected together into a special communication network over a Level
4 (or higher) high speed, single twisted pair data cable. The Nexus LX User & Technical Guide describes all you need to know to
successfully install a Nexus project. Ask for it from your supervisor, from your employer or from your nearest Thomas & Betts product
supplier. The network cabling of the building must be installed as per the procedure detailed in the Nexus LX User & Technical Guide. No
mains or mains carrying cables are to be connected to the data terminals or cables.
NEXUS RF (WIRELESS SYSTEM)
The Nexus RF range of light fittings are designed to communicate via a proprietary RF network, however the electrical installation of the
fittings is identical to that of a standard non-monitored fitting.
#
Fault
Possible Causes
1
Lamp and LED not lit
AC mains supply not connected; or
AC mains supply turned off; or
Unit not inserted into the base properly; or
Test switch damaged
2
Lamp not lit but LED is lit
Lamp damaged; or
Lamp incorrectly inserted
3
Lamp is lit but LED not lit
Test switch damaged; or
Battery not connected
4
The lamp does not switch to emergency mode when the
test button is pressed
Test switch damaged
5
The lamp works momentarily on emergency when the test
button is pressed
Battery not yet charged (allow up to 16 hours)