Parameter
Specification
Bluetooth
BLE 5.0
RFID
MIFARE ISO/IEC 14443A RFID cards
Compatible mobile device operating sys-
tems
•
Android 4.4 or higher
•
iOS8 or higher
11.13
Cable specifications
11.13.1
AC input cable (Europe)
Parameter
Specification
EV charger station connection type
Terminal block and screw
Wire size for the terminal block (allowed)
Cross section: 10 to 2.5 mm
2
Wire size for the terminal block (recommen-
ded for 32A EV Charger stations)
Minimum cross-section 6 mm
2
Wire size for the terminal block (recommen-
ded for 16A EV Charger stations)
Minimum cross-section 2.5 mm
2
Strip length
10 mm
Cable shielding (optional)
The local rules require shielded cables.
The cable shielding must be connected to
the PE rail at the two ends of the cable.
Diameter of the phase conductors
Refer to the local rules.
Diameter of the PE conductor
The same as te diameter of the phase con-
ductors
•
Consult your local electrical codes for the correct wire size, based on the environ-
ment, the conductor type and the rating of the EVSE.
•
The wire cross-sectional area is based on the copper wire type.
11.13.2
AC input cable (North America)
Parameter
Specification
EV charger station connection type
Terminal block and screws
Wire size for the terminal block (allowed)
6 to 20 AWG
Wire size for the terminal block (recommen-
ded for 32A EV Charger stations)
Minimum 8 AWG
Wire size for the terminal block (recommen-
ded for 16A EV Charger stations)
Minimum 12 AWG
Strip length
10 mm
Cable shielding (optional)
The local rules require shielded cables.
The cable shielding must be connected to
the PE rail at the two ends of the cable.
Diameter of the phase conductors
Refer to the local rules.
Technical data
54
BCM.V3Y01.0-EN | 001