General setting values for reading:
Upper threshold voltage U
max
S1
R
0.50 ... 1.00 x U
n
Lower threshold voltage U
min
S2
R
0.10 ... 0.80 x U
n
Voltage difference value
∆
U
S3
R
0.02 ... 0.40 x U
n
Phase angle difference value
∆ϕ
S4
R
5 ... 50
°
Frequency difference value
∆
f
S5
R
0.02 ... 0.50 Hz
Operate time (dead time) for t
VC
S6
R
0.10 ... 20 s
Check time in command mode operation, t
check
S7
R
0.05 ... 300 s
Closing signal length t
pulse
S8
R
0.2 ... 20 s
(only in command mode operation)
Operate time of circuit breaker, t
CB13
(stage 1)
S9
R
0.05 ... 0.25 s
Operate time of circuit breaker, t
CB23
(stage 2)
S10
R
0.05 ... 0.25 s
Checksum of switchgroup SGF
S11
R
0 ... 255
Checksum of switchgroup SGB
S12
R
0 ... 255
Checksum of switchgroup SGR
S13
R
0 ... 255
Main settings
Upper threshold voltage U
max
S21
R,W,(P)
0.50 ... 1.00 x U
n
Lower threshold voltage U
min
S22
R,W,(P)
0.10 ... 0.80 x U
n
Voltage difference
∆
U
S23
R,W,(P)
0.02 ... 0.40 x U
n
Phase angle difference
∆ϕ
S24
R,W,(P)
5 ... 50
°
Frequency difference
∆
f
S25
R,W,(P)
0.02 ... 0.50 Hz
Operate time (dead time) t
VC
S26
R,W,(P)
0.10 ... 20 s
Check time in command mode operation, t
check
S27
R,W,(P)
0.05 ... 300 s
Closing signal length t
pulse
S28
R,W,(P)
0.2 ... 20 s
(only in command mode operation)
Operate time of circuit breaker t
CB13
(stage 1)
S29
R,W,(P)
0.05 ... 0.25 s
Operate time of circuit breaker t
CB23
(stage 2)
S30
R,W,(P)
0.05 ... 0.25 s
Checksum of switchgroup SGF
S31
R,W,(P)
0 ... 255
Checksum of switchgroup SGB
S32
R,W,(P)
0 ... 255
Checksum of switchgroup SGR
S33
R,W,(P)
0 ... 255
Second settings
Upper threshold voltage U
max
S41
R,W,(P)
0.50 ... 1.00 x U
n
Lower threshold voltage U
min
S42
R,W,(P)
0.10 ... 0.80 x U
n
Voltage difference
∆
U
S43
R,W,(P)
0.02 ... 0.40 x U
n
Phase angle difference
∆ϕ
S44
R,W,(P)
5 ... 50
°
Frequency difference
∆
f
S45
R,W,(P)
0.02 ... 0.50 Hz
Operate time (dead time) t
VC
S46
R,W,(P)
0.10 ... 20 s
Check time in command mode operation, t
check
S47
R,W,(P)
0.05 ... 300 s
Closing signal length t
pulse
S48
R,W,(P)
0.2 ... 20 s
(only in command mode operation)
Operate time of circuit breaker t
CB13
(stage 1)
S49
R,W,(P)
0.05 ... 0.25 s
Operate time of circuit breaker t
CB23
(stage 2)
S50
R,W,(P)
0.05 ... 0.25 s
Checksum of switchgroup SGF
S51
R,W,(P)
0 ... 255
Checksum of switchgroup SGB
S52
R,W,(P)
0 ... 255
Checksum of switchgroup SGR
S53
R,W,(P)
0 ... 255