27
Data to be
transferred over
the serial bus
In addition to the event code data transfer, the
input data (I data), output data (O data), set-
ting values (S), memorized data (V data) and
some other data can be read from the relay
module over the serial communication bus.
Further, part of the data can be changed over
the SPA bus by separate commands. All data
information is available in channel 0.
Data
Code
Data
Value
direction
Input data
Measured voltage value U1
I1
R
0.00 ... 1.3 x U
n
Measured voltage value U2
I2
R
0.00 ... 1.3 x U
n
Measured voltage value U3
I3
R
0.00 ... 1.3 x U
n
Measured voltage difference value U1-U3
I4
R
0.00 ... 1.3 x U
n
Measured voltage difference value U2-U3
I5
R
0.00 ... 1.3 x U
n
Measured frequency value of U3
I6
R
45.0 ... 65.0 Hz
Measured frequency difference value U1-U3
I7
R
±
0.00 ...
±
20.0 Hz
999 = not measurable
Measured frequency difference value U2-U3
I8
R
±
0.00 ...
±
20.0 Hz
999 = not measurable
Measured phase angle difference value U1-U3
I9
R
0 ...
±
180
°
999 = not measurable
Measured phase angle difference value U2-U3
I10
R
0 ...
±
180
°
999 = not measurable
External command signal CS13
I11
R
0 = not active
1 = active
External command signal CS23
I12
R
0 = not active
1 = active
External blocking signal BS13
I13
R
0 = not active
1 = active
External blocking signal BS23
I14
R
0 = not active
1 = active
Output data
Starting of SC13
O1
R
0 = not started
(U
max
conditions are fulfilled)
1 = started
SC13 closing
O2
R
0 = not closed
1 = closed
Starting of VC13
O3
R
0 = not started
1 = started
VC13 closing
O4
R
0 = not closed
1 = closed
Starting of SC23
O5
R
0 = not started
(U
max
conditions are fulfilled)
1 = started
SC23 closing
O6
R
0 = not closed
1 = closed
Starting of VC23
O7
R
0 = not started
1 = started
VC23 closing
O8
R
0 = not closed
1 = closed
Closing signal CB13
O9
R,W,(P) 0 = not active
1 = active
Closing signal CB23
O10
R,W,(P) 0 = not active
1 = active
Output signal ALARM
O11
R,W,(P) 0 = not active
1 = active
Operation of output relays, ENA signal
O41
R,W,(P) 0 = not operated
1 = operated
Memorized output signal ALARM
O21
R
0 = no alarm
1 = alarm