36
Measured and
recorded parameter
values
Measured value
Para-
Data
Value
meter
direction
Last 15 min maximum demand current
V1
R
0…2.5 x I
n
Number of starts of stage I>
V2
R
0…255
Number of starts of stage I>>
V3
R
0…255
Number of starts of stage I
0
>
V4
R
0…255
Number of starts of stage I
0
>>
V5
R
0…255
Number of starts of stage
∆
I>
V6
R
0…255
Stage/phase that caused operation
V7
R
1 = I
L3
>, 2 = I
L2
>,
4 = I
L1
>, 8 = I
0
>,
16 = I
L3
>>, 32 = I
L2
>>,
64 = I
L1
>>, 128 = I
0
>>
Stage/phase that caused operation
V8
R
1 = I
L3
>>>, 2 = I
L2
>>>,
4 = I
L1
>>>
Operation indication code on the display
V9
R
0…12
Maximum 15 min demand current
V10
R
0…2.55 x I
n
The last five recorded values can be read (R)
with parameters V11…V59. Event n denotes
the youngest recorded value and n-1 the next
youngest and so forth.
Registered value
Event
Measuring
n
n-1
n-2
n-3
n-4
range
Phase current I
L1
V11
V21
V31
V41
V51
0…63 x I
n
(register 1)
Phase current I
L2
V12
V22
V32
V42
V52
0…63 x I
n
(register 2)
Phase current I
L3
V13
V23
V33
V43
V53
0…63 x I
n
(register 3)
Earth-fault current I
0
V14
V24
V34
V44
V54
0…21 x I
n
(register 6)
Difference current
∆
I
V15
V25
V35
V45
V55
0…100%
(register 9)
Start duration, stage I>
V16
V26
V36
V46
V56
0…100%
(register 4)
Start duration, stage I>>
V17
V27
V37
V47
V57
0…100%
(register 5)
Start duration, stage I
0
>
V18
V28
V38
V48
V58
0…100%
(register 7)
Start duration, stage I
0
>>
V19
V29
V39
V49
V59
0…100%
(register 8)