14
Setting
Description
Setting range
(Default value)
Final trip
Selection of operation mode for signals AR1...3:
AR1 (the third digit from the right
0...1
AR2( the second digit from the right)
0...1
AR3 (the right-most digit)
0...1
(000)
0 = no final trip signal from the AR module (No)
1 = final trip signal from the AR module (Yes)
Submenu 1:
Selection of operation mode for signal AR4
0...1
(the right-most digit):
(--0)
0 = no final trip signal from the AR module (No)
1 = final trip signal from the AR module (Yes)
Operate time of final tripping when
2nd submenu:
- initiated by signal AR1
0...5.0 s (0 s)
3rd submenu:
- initiated by signal AR2
0...5.0 s (0 s)
4th submenu:
- initiated by signal AR3
0...5.0 s (0 s)
5th submenu:
- initiated by signal AR4
0...5.0 s (0 s)
t
r
Reclaim time
0.2...300 s (10 s)
1st submenu:
Lenght of CB closing signal
0.1...2.0 s (0.2 s)
2nd submenu:
Lenght of CB opening signal
0.1...2.0 s (0.2 s)
Note! The control signals are interrupted once
information about change in CB position is received
t
d
Discriminating time of AR shot 1
0...30 s (0 s)
1st submenu:
Discriminating time of AR shot 2
0...30 s (0 s)
2nd submenu:
Discriminating time of AR shot 3
0...30 s (0 s)
3rd submenu:
Discriminating time of AR shot 4
0...30 s (0 s)
Switchgroups
See "Configuration switchgroups" for more details
SGF
Switchgroups for the configuration of functions
0...255
SGB
Switchgroups for the configuration of blocking and
control signals
0...255
SGR
Switchgroups for the configuration of the output relays
0...255
Maintenance monitor
Stress factor for CB opening
1
- manual operation
0...50 (0)
1st submenu:
- initiated by signal AR1
0...50 (0)
2nd submenu:
- initiated by signal AR2
0...50 (0)
3rd submenu:
- initiated by signal AR3
0...50 (0)
4th submenu:
- initiated by signal AR4
0...50 (0)
2
Value of CB maintenance monitor
0...999 (999)
1st submenu:
Pre-alarm level
0...50 (0)