SM3000
Multipoint Videographic Recorder
6 Configuration
88
IM/SM3000–EN Rev. L
'Chart view enable' set to 'Vertical', 'Horizontal -->' or 'Horizontal <--'
OR
'Chart view enable' set to 'Circular'
Each recording channel can be configured to position its trace in
a specific zone in the vertical or horizontal chart views in order to
separate traces that would otherwise be very close to each
other.
Select one of the 15 pre-defined or 10 custom zones available –
see Section 6.8.2, page 108 for custom zone configuration
details.
Select the filter to be applied to the electrical input prior to
sampling.
Notes.
Applicable to analog sources only.
Filters are applied to the recorded values shown on the
chart view only, not to instantaneous values displayed on
the channel indicators or bargraphs.
Instantaneous – A single value based on process conditions at
the time of sampling.
Average
– The average value of the analog signal since
the previous sample.
Minimum
– The minimum value of the analog signal since
the previous sample.
Maximum
– The maximum value of the analog signal since
the previous sample.
Max
&
min
– Two values are recorded to capture the
maximum & minimum signal values since the
previous sample. This allows the memory use
to be extended by permitting a slower sample
rate to be selected without losing the transient
behavior of the signal.
•1
If this parameter is changed, a new internal data file for this recording channel is created. All historical data stored internally for
this channel is lost.
1
Raw
Input
Value
Instantaneous Value at time of sample
Sample Interval
Minimum Value over sample interval
Average Value over sample interval
Maximum Value over sample interval
12:00:00
(Previous
Sample)
12:00:01
(Current
Sample)
0
100
t