6 Configuration
66
IM/SM3000–EN Rev. L
Enter the number of consecutive incorrect password entries
allowed by a user. If the number of incorrect entries exceeds this
limit, the user's access privileges are de-activated and can be
reinstated only by the System Administrator (User 1).
Passwords have a maximum length of 20 characters. Enter the
minimum length required for all new passwords.
The System Administrator (User 1) can view and/or change the
user name, access privileges and password for any other user.
Select the user to be viewed/edited.
Enter a name for the selected user.
Set access privileges for selected user.
Disabled
– The selected user is unable to access the
Configuration and Setup levels or enter
electronic signatures.
Setup
– The selected user is able to access the
Setup level.
e-Sign
– The selected user is able to enter an
electronic signature.
Config
(Full)
– The selected user is allowed full
configuration access with the exception of
access to the Audit Log size setting and the
Security Settings.
Note.
The System Administrator (User 1) only is able to change
the Audit Log size and the Security Settings.
Config (Ltd)
– The selected user is able to:
• Change alarm trip points, hysteresis and
time hysteresis settings.
• Make input adjustments for analog input
boards.
• Load configurations from external media
only.
Config (Load) – The selected user is unable to make any
configuration changes but can load
configurations from external media.
Enter an initial password for the selected user.
Note.
The user may subsequently change this password.