SM3000
Multipoint Videographic Recorder
6 Configuration
108
IM/SM3000–EN Rev. L
6.8.2 Custom Chart Zones
6.8.3 Real-time Alarms
For each custom chart zone, set the lower and upper margins of
the zone, between 0.00 and 100.00 %.
Example.
If the lower and upper margins for Custom zone 1
are set to 10 and 25 % respectively, the trace for a recording
channel assigned to 'Custom 1' (see Section 6.6.1, page 87) is
confined to that area of the chart that lies between 10 and 25 %
of:
a vertical chart's width from the left hand edge
a horizontal chart's height from the bottom
Enter the tag to be used in the Alarm Event log – see
Section 4.9, page 37.
Set the day(s) on which the alarm is activated.
Set to 'On' to activate the real-time alarm on the first day of
each month.
Set the time at which the alarm becomes active.
If 'Every hour' is set to 'On', the 'Hours' setting cannot be
adjusted and the alarm is activated at the same time every hour
(determined by the 'Minutes' setting) or on the hour (if 'Minutes'
is set to 'Off').
Set the duration for the alarm to remain active.
Set to 'On' to add an entry to the Alarm event log each time the
real-time alarm becomes active.