SensyMaster FMT230, FMT250
THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C
77
Modbus register
address (application)
Parameter name
Data type [register length] /
value range
Description
6006 (1), 6016 (2),
6026 (3), 6036 (4),
6046 (5), 6056 (6),
6066 (7), 6076 (8)
Gas Type 6
Gas type and concentration for gas components 1 ... 10 of a gas mix.
7011 (1), 7031 (2),
7051 (3), 7071 (4),
7091 (5), 7111 (6),
7131 (7), 7051 (8)
Concentr. Gas Type 6
The value range depends on the concentration of gas types with a
smaller index.
Maximum 0 ... 16.67 %.
6007 (1), 6017 (2),
6027 (3), 6037 (4),
6047 (5), 6057 (6),
6067 (7), 6077 (8)
Gas Type 7
7013 (1), 7033 (2),
7053 (3), 7073 (4),
7093 (5), 7113 (6),
7133 (7), 7053 (8)
Concentr. Gas Type 7
The value range depends on the concentration of gas types with a
smaller index.
Maximum 0 ... 14.29 %.
6008 (1), 6018 (2),
6028 (3), 6038 (4),
6048 (5), 6058 (6),
6068 (7), 6078 (8)
Gas Type 8
7015 (1), 7035 (2),
7055 (3), 7075 (4),
7095 (5), 7115 (6),
7135 (7), 7055 (8)
Concentr. Gas Type 8
The value range depends on the concentration of gas types with a
smaller index.
Maximum 0 ... 12.5 %
6009 (1), 6019 (2),
6029 (3), 6039 (4),
6049 (5), 6059 (6),
6069 (7), 6079 (8)
Gas Type 9
7017 (1), 7037 (2),
7057 (3), 7077 (4),
7097 (5), 7117 (6),
7137 (7), 7057 (8)
Concentr. Gas Type 9
The value range depends on the concentration of gas types with a
smaller index.
Maximum 0 ... 11.11 %
6010 (1), 6010 (2),
6030 (3), 6040 (4),
6050 (5), 6060 (6),
6070 (7), 6080 (8)
Gas Type 10
7019 (1), 7039 (2),
7059 (3), 7079 (4),
7099 (5), 7119 (6),
7139 (7), 7059 (8)
Concentr.Gas Type 10
The value range depends on the concentration of gas types with a
smaller index.
Maximum 0 ... 10 %
… / Sensor / ...Application 1 ... 8 / ...A2...Field Optim. – ...A8...Field Optim.
7171 (1), 7217 (2),
7263 (3), 7309 (4),
7355 (5), 7401 (6),
7447 (7), 7493 (8)
Offset Qm
TFLOAT [2]
Offset correction of the flow rate measured value.
7173 (1), 7219 (2),
7265 (3), 7311 (4),
7357 (5), 7403 (6),
7449 (7), 7495 (8)
Corr.Factor Qm
TFLOAT [2]
Correction factor for the flow measured value.