SensyMaster FMT230, FMT250
THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C
87
Modbus register
address
Parameter name
Data type [register length] /
value range
Description
Setting of the simulated measured values. The simulated value is selected with the parameter ‘Simulation Switch’.
4003
Dig.Out 41/42 State
TUSIGN8 [1]
0 - Off
1 - On
The respective simulated output value is dependent on the operating mode (pulse
/ frequency) of the digital output 41 / 42.
5017 Freq.Out
41/42
Puls.Out 41/42
TFLOAT [2]
0 to 10500 Hz 0 to 10500 pulses
4004 Dig.Out
51/52
State
TUSIGN8 [1]
0 - Off
1 - On
5019 Dig.Out
51/52
Pulse
TFLOAT [2]
0 to 10500 pulses
Only if the digital output 51 / 52 has been configured as a pulse output.
5003
Mass Flow [unit]
TFLOAT [2]
0 to 2 x QmMax DN
Setting of the simulated measured values. The simulated value is selected with
the parameter ‘Simulation Switch’.
5011
Mass Flow [%]
TFLOAT [2]
-200 to 200 %
5007 Qv@
Vol.flow
[unit]
TFLOAT [2]
0 to 2 x QvMax DN
5015 Qv@
Vol.flow
[%]
TFLOAT [2]
-200 to 200 %
5001 Temperature
[unit]
TFLOAT [2]
−
100 to 250 °C
5009 Temperature
[%]
TFLOAT [2]
-200 to 200 %
... / ...Output Readings
239 Freq.Out
41/42
TFLOAT [2]
0 to 10500 Hz
Output of the current output values. The available values are dependent on the
configuration of the digital outputs.
The parameters are read only.
18
Dig.Out 41/42 State
TUSIGN8 [1]
0 - Off
1 - On
241 Freq.Out
51/52
TFLOAT [2]
0 to 10500 Hz
19 Dig.Out
51/52
State
TUSIGN8 [1]
0 - Off
1 - On