INSTALLATIONS
A clean, flat surface capable of supporting the Package Compact Substation unit weight is the
only requirement for a foundation. It is, however, important that adequate accessibility,
ventilation and ease of inspection of the unit must be provided.
In all installation work, the safety regulations for electrical installations have to be observed.
CONNECTIONS
Each Package Compact Substation must be permanently grounded or earthed by connecting an
affective recognised ground or earth as prescribed by the latest applicable edition of IEC or
ANSI requirements.
The Package Compact Substation is designed to operate with a solidly grounded neutral system.
The neutral connection should be solidly and permanently grounded.
Tap connections
SAFETY NOTES FOR OPERATIONS
1.
DO NOT LIFT OR MOVE A TRANSFORMER OR PACKAGE COMPACT
SUBSTATION WITHOUT ADEQUATE EQUIPMENT AND PRECAUTIONS.
2.
TERMINALS ARE FOR ELECTRICAL LOADING ONLY.
3.
DO NOT MAKE ANY CONNECTIONS THAT ARE NOT
AUTHORIZED
BY THE
NAMEPLATE OR CONNECTION DIAGRAMS.
4.
DO NOT ENERGIZE THE SUBSTATION WITHOUT PROPERLY MADE GROUND
OR EARTH CONNECTIONS.
5.
DO NOT ATTEMPT TO CHANGE THE TAP SETTINGS WHILE THE
TRANSFORMER IS ENERGIZED FROM EITHER THE HIGH VOLTAGE OR LOW
VOLTAGE SIDE.
6.
DO NOT CHANGE CONNECTIONS OF A TRANSFORMER THAT IS UNDER
EXCITATION.
7.
DO NOT TAMPER WITH INTERLOCKS, ALARM AND CONTROL CIRCUIT.
8.
DO NOT REMOVE COVER PLATES OR ACCESSORIES WHILE THE SUBSTATION
IS ENERGIZED.
WARNING
WARNING WARNING WARNING WARNING WARNING
BEFORE ENERGIZING OR PLACING ANY UNIT INTO SERVICE AFTER EXTENDED
STORAGE, A CHECK OF THE INSULATION RESISTANCE
SHOULD BE MADE.
WARNING WARNING WARNING WARNING WARNING WARNING
A POOR GROUND OR EARTHING MAY RESULT IN LOSS OF LIFE OR
DAMAGE TO THE EQUIPMENT. AN EFFECTIVE LOW RESISTANCE
GROUND IS ESSENTIAL FOR PROPER OPERATION.