3. SACE PR212/MP
protection release
10. Using the arrow keys, set I-F=2.00:
11. Select the phase (or phases) on which to simulate the
fault current.
(L1+L2+L3)
12. Press ENTER to activate fault simulation.
S-PROT: t=k, ON
I2: 1.0 In => 400 A
T2: 0.5 s
I-f: 2.00 => 800 A(*)
(*) In this example, the
automatically identified
rating of the current
sensor is 400A.