ABB | SACE Emax 2
120 | © 2013
ABB |
1SDH001000R0002 - L7804
Ekip Touch protection release | 13 - G Hi-Touch protections
Continued from the previous page
Parameters
It is possible to modify various parameters:
Parameter
Description
Enabling
Activates/deactivates the protection.
Curves
Defines the variation dynamic of the current threshold, as represented
in the two diagrams above.
Current
Threshold (I21)
It defines the current value that if exceeded activates the protection (in
reference to the curve, it is the part parallel to the ordinate).
It is represented both as an absolute value (Ampere) and as a relative
value (In, nominal value defined by the Rating Plug).
Threshold Ul2
(Step)
With the curve in step mode, is the threshold that determines the
variation of the level of I21:
• With voltage
≥
Ul2, the tripping threshold is I21.
• With voltage < Ul2, the tripping threshold is Ks * I21.
It is represented both as an absolute value (Volts) and as a percentage
(of Vn, a nominal value defined on the release).
Uh2 and Ul2
Threshold
(Linear)
With the curve in linear mode, it is the threshold that determines the
variation of the level of I21:
• With voltage
≥
Uh2, the tripping threshold is I21.
• With voltage < Uh2 and > Ul2, the tripping threshold changes
gradually.
• With voltage
≤
Ul2, the tripping threshold is Ks * I21.
It is represented both as an absolute value (Volts) and as a percentage
(of Vn, a nominal value defined on the release).
Threshold Ks2
Constant for calculation of the variation of the I21 threshold. To be
applied in different ways according to the type curve selected.
Time (t21)
This is the delay time between the exceeding of the I21 threshold
(determined by the voltage value read) and the sending of the opening
command (in reference to the curve, t21 affects the entire curve,
moving it along the vertical axis).
The protection S2 (V) has
Trip Enable
, see page 93.