![ABB RobotWare 7.7 Скачать руководство пользователя страница 77](http://html.mh-extra.com/html/abb/robotware-7-7/robotware-7-7_applications-manual_5111077.webp)
xx1800000143
Note
The
Upgrade
button is enabled only if a new version is detected either in
the default firmware path or in a browsed path.
7 Click
Upgrade
.
The firmware is upgraded and a message is displayed.
Upgrade firmware from the FlexPendant
Note
Firmware upgrade is not available for Safe digital base devices or for attached
Add-ons.
1 Set the OmniCore controller in manual mode.
2 On the start screen, tap
I/O
, and then select
I/O Devices
from the menu.
3 If the I/O device is in the running state, select the device and and tap
Deactivate
.
4 Select the I/O device and and tap
Firmware Update
.
Note
Firmware upgrade is not possible if the state of the selected I/O device is
Running
.
Continues on next page
Application manual - Scalable I/O
77
3HAC070208-001 Revision: F
© Copyright 2019-2022 ABB. All rights reserved.
4 Software commissioning
4.6 Firmware upgrade
Continued