GUID-4412CDB6-8215-4C94-AF11-0CF8EEC6F4D2 V1 EN
Figure 88:
Detecting unresponsive IED or incorrect IED type
3.
Accept the technical keys suggested by PCM600. If the device’s technical
key is, for example, “RIO600” or “BAY1” and a new device instance is
created in online mode, an error message appears. Click
Yes
to change the
technical key or
No
to abort the scan.
9.2
Troubleshooting the reading and writing of
parameters
Common validations while reading and writing parameters
•
Ensure that the device is online.
•
Ensure that the device contains a valid configuration. Composition of IED and
IED object in PCM should match.
•
Ensure that the composition selection matches with the device. Technical key
in IED and PCM should match.
•
Ensure that the technical key is correct.
Validations while writing parameters
•
Check that the IRF Module number is either zero or corresponds to any of the
DOM module positions.
Section 9
1MRS757489 A
Troubleshooting
76
RIO600
Configuration Manual