When the device is already connected to PCM600 and the communication is
established, PCM600 can read the configuration directly from the physical device.
This is useful when an order-specific device is used. The order configuration is
written to the device at the factory and PCM600 is able to access it.
If the device is not configured or it contains an invalid configuration, select
Write
to IED
before any other operations in the online mode. If the device has a valid
configuration, select
Read from IED
directly after the device instance has been
created to retain the communication parameter’s value. In Parameter Setting tool,
the communication parameters are then updated according to the device
configuration. Otherwise, the Parameter Setting tool contains the default data, for
example, the default IP Address
192.168.2.10
.
3.4.1
Inserting an IED in offline mode
1.
In the
Plant Structure
view, right-click the bay and select
New/Remote I/O
IEDs/RIO600
.
The
Configuration mode selection page
dialog box opens.
2.
Under
Configuration mode
, select
Offline Configuration
and click
Next
.
GUID-C9A317A6-0D51-4745-B3BA-48F0E125FF2B V1 EN
Figure 16:
Selecting offline configuration mode
3.
In the
IED protocol
list, select for example
IEC 61850
and click
Next
.
Section 3
1MRS757489 A
Setting up a project
18
RIO600
Configuration Manual