3.1. Select
Don't import IEDs of unknown type
to protect the existing
IEDs in case the SCD file does not match the original configuration in
PCM600.
3.2. Select
Replace unknown IED types with generic IEC 61850 object
type
, if it is known that the file includes additional IEDs that are
needed. The Generic IEC 61850 IED type is used to integrate these
IEDs into the plant structure.
3.3. Select
Ignore PCM Object Type
to update the IED object(s) in
PCM600 from the IED type(s) in the SCD file, whether or not the IED
type(s) in the SCD file matches the IED object(s) in PCM600.
3.4. Select
Ignore Substation Section
to not import the SSD file part of the
SCD file.
GUID-5750D3FF-C120-40E9-858D-24D7962A2CC7 V1 EN
Figure 52:
Importing SCD file
4.
Make connections from the sending devices (publisher) to the receiving
function blocks (subscriber) with the
Signal Matrix tool
.
The GOOSE connection can have only one output for any of
the hardware modules. The PCM600 level validation is done
for a duplicate connection. A DOM to DOM connection is not
provided in the current version.