1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
15
5RJRZVNLFRLO
9ROWDJHGLYLGHU
Primary values and measurement device settings
The conversion between primary and per unit values are based on the analogue
scales of the I
L1
(I
L1
pu-scale), I
0
(I
0
pu-scale), I
0b
(I
0b
pu-scale), U
12
(U
12
pu-scale)
and U
0
(U
0
pu-scale). To ensure proper operation, it must be checked that the
analogue scales of the phase currents I
L1
, I
L2
and I
L3
, and correspondingly, the
analogue scales of the phase-to-phase voltages U
12
, U
23
and U
31
are identical.
4.1.7.
Digital inputs
The digital inputs of the protection relay are voltage-controlled and optically
isolated. For technical data of the digital inputs, refer to Table 4.2.1-3 on page 31.
4.1.7.1.
Filtering of digital inputs
The filter time eliminates debounces and short disturbances on digital inputs. The
filter time may be set individually for each input.
)LJ )LOWHULQJRIDGLJLWDOLQSXW
Phase displacement error at voltage U
n
(d = error in degrees)
Phase displacement error = - d
Amplitude error at the whole measuring range
(e = error in per cent)
Amplitude correction factor
= 1/(1+ e/100)
Phase displacement error at the whole
measuring range
(e = error in degrees)
Phase displacement error = - e
Amplitude error at the whole measuring range
(e = error in per cent)
Amplitude correction factor
= 1/(1+ e/100)
Phase displacement error at the whole
measuring range
(e = error in degrees)
Phase displacement error = - e