54
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
Commands
Explanations to the Table 11.5.-2:
1)
Note! When controlling the output relays by using the IEC_103 protocol, the
interlocking of the standard configuration is bypassed. It is not allowed to use the
same output relay as a tripping contact and as an IEC_103 controlling object
simultaneously.
St
Status
A
According to the IEC 60870-5-103 standard
B
According to “Digitale Stationsleittechnik - Ergänze Empfehlungen zur
Anwendung in Verteilnetzstationen”
P
Private definition
Ftyp
Function type
Note: If stated as *), the signal type Ftyp corresponds with the unit function
type. Unit function type may be adjusted via the “Function type” parameter.
InfNum
Information element number
COT cmd
Cause of transmission values in command direction
20
General command
COT resp
Cause of transmission values in response direction
20
Positive acknowledgement
21
Negative acknowledgement
Table 11.5.-2 Commands
1)
Commands
St
Ftyp
Inf
Num
Typ
COT
cmd
COT
resp
I<->0
CB1: control CB1
B
240
160
20
20
20,21
Output relay 1 control (HSPO1)
P
251
27
20
20
20,21
Output relay 2 control (PO1)
P
251
28
20
20
20,21
Output relay 3 control (PO2)
P
251
29
20
20
20,21
Output relay 4 control (PO3)
P
251
30
20
20
20,21
Output relay 5 control (SO1)
P
251
31
20
20
20,21
Output relay 6 control (SO2)
P
251
32
20
20
20,21