![ABB REU615 Скачать руководство пользователя страница 37](http://html.mh-extra.com/html/abb/reu615/reu615_applications-manual_2847037.webp)
Binary input
Default usage
Connector pins
X130-BI1
Blown primary fuse indication
X130-1,2
X130-BI2
Line voltage transformer MCB open
X130-2,3
X130-BI3
Bus voltage transformer MCB open
X130-4,5
X130-BI4
Lockout reset
X130-5,6
Table 10:
Default connections for binary outputs
Binary output
Default usage
Connector pins
X100-PO1
X100-6,7
X100-PO2
In synchronism for close
X100-8,9
X100-SO1
General start indication
X100-10,11,(12)
X100-SO2
General operate indication
X100-13,14
X100-PO3
Open circuit breaker/trip coil 1
X100-15-19
X100-PO4
Open circuit breaker/trip coil 2
X100-20-24
X110-SO1
Load shedding group 1
X110-14,15,16
X110-SO2
Load shedding group 2
X110-17,18,19
X110-SO3
Load restore group 1
X110-20,21,22
X110-SO4
Load restore group 2
X110-23,24
Table 11:
Default connections for LEDs
LED
Default usage
1
Overvoltage protection operated
2
Undervoltage protection operated
3
Residual voltage protection operated
4
Sequence voltage protection operated
5
Frequency protection operated
6
Load shedding operated
7
Disturbance recorder triggered
8
Systems synchronized
9
Voltage transformer secondary MCB open
10
Arc fault detected
11
Primary voltage transformer fuse blown
3.4.2.2
Default disturbance recorder settings
1MRS757054 A
Section 3
REU615 standard configurations
REU615
31
Application Manual