ABB Substation Automation
Products and Systems
User’s Guide
REU 513
46
1MRS750886-MUM
Control parameters
Table 27: Control parameters
Description
Para-
meter
R/W
Value
Resetting of output contacts with
the latching feature
V101
W
1=reset
Resetting of registers and output
contacts with the latching feature
V102
W
1=reset
Rated frequency
V133
R,W (P)
50=50 Hz
60=60 Hz
Nominal voltage
V134
R,W (P)
100, 110, 115, 120 (V)
Remote control of settings
V150
R,W
0=setting group 1
1=setting group 2
Event mask for U> and U>>
V155
R,W
0...255, see Event codes
Event mask for U< and U<<
V156
R,W
0...255, see Event codes
Event mask for output contacts’
events
V157
R,W
0...255, see Event codes
Event mask for disturbance
recorder
V158
R,W
0 / 1, see Event codes
Entering the password for
settings
V160
W
1...999
Changing the password or
reinstating password protection
V161
W (P)
1...999
Activating the self-supervision
READY LED
V165
W
0=normal operation
1=self-supervision READY LED
blinking
LED test for start and trip
indicators
V166
W (P)
0=start and trip LEDs off
1=trip LED on, start LED off
2=start LED on, trip LED off
3=start and trip LEDs on
Default settings
V167
W (P)
2=Restore factory settings
Internal fault code
V169
R
0...255
SPA address of the relay
V200
R, W
1...254
Data transfer rate, kbps
V201
R, W
4.8 or 9.6
Relay serial number
V230
R
ERxxxxxx
CPU serial number
V231
R
MRxxxxxx
Hardware number
V232
R
1MRS090405-BAA
Test date
V233
R
YYYYMMDD