Explanations for default values:
0 = not included in event reporting
1 = included in event reporting
Events E50 and E51 are always included in event reporting.
Table 17: Event codes E17…E24
Code
Event
Weighting factor
Default value
E17
PO1 activated
1
1
E18
PO1 reset
2
1
E19
PO2 activated
4
0
E20
PO2 reset
8
0
E21
SO1 activated
16
0
E22
SO1 reset
32
0
E23
SO2 activated
64
0
E24
SO2 reset
128
0
Default value of event mask V157
3
Table 18: Event code E31
Code
Event
Weighting factor
Default value
E31
Disturbance recorder triggered
1
1
Default value of event mask V158
1
Table 19: Event codes E50 and E51
Code
Event
E50
Restart of relay
E51
Overflow of event register