8
R E M 61 5 A N S I 5.0 FP1
M OTO R P R OT EC T I O N A N D CO N T R O L
—
Table 1. Standard configurations
Description Std. conf.
Basic motor protection (RTD option)
A
Motor protection with voltage & frequency based protection and measurements (RTD option), remanent voltage
B
Motor protection with voltage & frequency based protection and measurements (Sensor inputs), remanent voltage
D
Differential (core balance and true), overcurrent, load loss, phase and neutral voltage, frequency and RTD protection, power protection and
power system metering for medium to large motors
E
—
Table 2. Supported functions
Function
IEC 61850
ANSI
A
B
D
E
Protection
Three-phase non-directional overcurrent protection, low stage
PHLPTOC
51P
1
1
1
1
Three-phase non-directional overcurrent protection, high stage PHHPTOC
50P
1
(19)
1
(19)
1
(19)
2
Three-phase non-directional overcurrent protection,
instantaneous stage
PHIPTOC
50P-3
1
1
1
1
Non-directional earth-fault protection, low stage
EFLPTOC
51G
1
(4)
1
(4)
Non-directional earth-fault protection, high stage
EFHPTOC
50G
1
(4)
1
(5)
1
(5)
2
(4)
Directional earth-fault protection, low stage
DEFLPDEF
67/51N
1
(4), (10)
1
(4), (10)
1
Residual overvoltage protection
ROVPTOV
59G/59N
1
1
Three-phase undervoltage protection
PHPTUV
27
1
1
2
Three-phase overvoltage protection
PHPTOV
59
2
Positive-sequence undervoltage protection
PSPTUV
27PS
1
1
1
Negative-sequence overvoltage protection
NSPTOV
47
1
1
2
Three-phase remnant undervoltage protection
MSVPR
27R
1
1
1
Frequency protection
FRPFRQ
81
2
2
2
Overexcitation protection
OEPVPH
24
2
Negative-sequence overcurrent protection for machines
MNSPTOC
46M
2
2
2
2
Loss of load supervision
LOFLPTUC
37M
1
1
1
2
Motor load jam protection
JAMPTOC
51LR
1
1
1
2
Motor start-up supervision
STTPMSU
66/51LRS
1
1
1
1
Phase reversal protection
PREVPTOC
46R
1
1
1
1
Thermal overload protection for motors
MPTTR
49M
1
1
1
1
Motor differential protection
MPDIF
1
High-impedance differential protection for phase A
HIAPDIF1
87A
1
IA, (BS)
High-impedance differential protection for phase B
HIBPDIF
87B
1
IB, (BS)
High-impedance differential protection for phase C
HICPDIF
87C
1
IC, (BS)
Circuit breaker failure protection
CCBRBRF
50BF
1
1
1
1
Master trip
TRPPTRC
86/94
1
1
(19)
(3)
(22)
(3)
(6)
1
1
(19)
(3)
(22)
(3)
(6)
2
(3)
(22)
(3)
(6)
2
(3)
(22)
(3)
(6)
Arc protection
ARCSARC
AFD
(3)
(3)
(3)
(3)
Multipurpose protection 2)
MAPGAPC
MAP
3
15
(19)
3
15
(19)
18
(19)
18
(19)
Underpower protection
DUPPDPR
32U
2
Reverse power/ directional overpower protection
DOPPDPR
32O
3
Control
Circuit breaker control
CBXCBR
52
1
1
1
1
Disconnector control
DCXSWI
29DS
219)
219)
219)
219)
Earthing switch control
ESXSWI
29GS
119)
119)
119)
119)
Disconnector position indication
DCSXSWI
52-TOC, 29DS
119)
219)
119)
219)
1
219)
1
219)
Содержание REM615 ANSI 5.0 FP1
Страница 1: ... PRODUCT GUIDE REM615 ANSI 5 0 FP1 Motor protection and control ...
Страница 49: ...49 Figure 17 Terminal diagram of standard configuration B ...
Страница 50: ...50 REM615 ANSI 5 0 FP1 MOTOR PROTECTION AND CONTROL Figure 18 Terminal diagram of standard configuration D ...
Страница 55: ...55 ...