25
—
Table 14. Double-pole power output relays with TCS function
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC (two contacts connected in series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Trip-circuit supervision (TCS):
• Control voltage range
• Current drain through the supervision circuit
• Minimum voltage over the TCS contact
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
—
Table 15. Single-pole power output relays
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
—
Table 16. High-speed output HSO with BIO0007
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
6 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC
5 A/3 A/1 A
Operate time
<1 ms
Reset
<20 ms, resistive load
—
Table 17. Front port Ethernet interfaces
Ethernet interface
Protocol
Cable
Data transfer rate
Front
TCP/IP protocol
Standard Ethernet CAT 5 cable with
RJ-45 connector
10 MBits/s
—
Table 18. Station communication link, fiber optic
Connector
Fiber type
(1)
Wave length
Typical max.
length
(2)
Permitted path attenuation
(3)
LC
MM 62.5/125 or 50/125
μ
m
glass fiber core
1300 nm
2 km
<8 dB
ST
MM 62.5/125 or 50/125
μ
m
glass fiber core
820...900 nm
1 km
<11 dB
1 (MM) multi-mode fiber, (SM) single-mode fiber
2 Maximum length depends on the cable attenuation and quality, the amount of splices and connectors in the path.
3 Maximum allowed attenuation caused by connectors and cable together