47
Function
Web HMI
PCM600
Relay parameter setting
•
•
Saving of relay parameter settings in the relay
•
•
Signal monitoring
•
•
Disturbance recorder handling
•
•
Alarm LED viewing
•
•
Access control management
•
•
Relay signal configuration (Signal Matrix)
—
•
Modbus® communication configuration (communication management)
—
•
DNP3 communication configuration (communication management)
—
•
IEC 60870-5-103 communication configuration (communication management)
—
•
Saving of relay parameter settings in the tool
—
•
Disturbance record analysis
—
•
XRIO parameter export/import
•
•
Graphical display configuration
—
•
Application configuration
—
•
IEC 61850 communication configuration, GOOSE (communication configuration)
—
•
Phasor diagram viewing
•
—
Event viewing
•
•
Saving of event data on the user's PC
•
•
Online monitoring
—
•
—
Table 85. Tools
• = supported
26. Cyber security
The relay supports role based user authentication
and authorization. It can store 2048 audit trail
events to a nonvolatile memory. The non-volatile
memory is based on a memory type which does not
need battery backup or regular component ex-
change to maintain the memory storage. FTP and
Web HMI use TLS encryption with a minimum of 128
bit key length protecting the data in transit. In this
case the used communication protocols are FTPS
and HTTPS. All rear communication ports and op-
tional protocol services can be deactivated accord-
ing to the required system setup.