28
R E M 61 5 A N S I 5.0 FP1
M OTO R P R OT EC T I O N A N D CO N T R O L
—
Table 24. Insulation tests
Description
Type test value
Reference
Dielectric tests
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
IEC 60255-27
IEEE C37.90-2005
Impulse voltage test
5 kV, 1.2/50
μ
s, 0.5 J
1 kV, 1.2/50
μ
s, 0.5 J, communication
IEC 60255-27
IEEE C37.90-2005
Insulation resistance measurements
>100 MΩ, 500 V DC
IEC 60255-27
Protective bonding resistance
<0.1 Ω, 4 A, 60 s
IEC 60255-27
—
Table 25. Mechanical tests
Description
Type test value
Reference
Vibration tests (sinusoidal)
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
Class 2
Shock and bump test
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
Class 2
Seismic test
IEC 60255-21-3
Class 2
—
Table 26. Environmental tests
Description
Type test value
Reference
Dry heat test
• 96 h at +55ºC
• 16 h at +85ºC
(1)
IEEE C37.90-2005
IEC 60068-2-2
Dry cold test
• 96 h at -25ºC
• 16 h at -40ºC
IEEE C37.90-2005
IEC 60068-2-1
Damp heat test
• 6 cycles (12 h + 12 h) at +25°C…+55°C,
humidity >93%
IEEE C37.90-2005
IEC 60068-2-30
Change of temperature test
• 5 cycles (3 h + 3 h)
at -25°C...+55°C
IEEE C37.90-2005
IEC60068-2-14
Storage test
• 96 h at -40ºC
• 96 h at +85ºC
IEEE C37.90-2005
IEC 60068-2-1
IEC 60068-2-2
1 For relays with an LC communication interface the maximum operating temperature is +70°C
—
Table 27. Product safety
Description
Value
LV directive
2006/95/EC
Standard
EN 60255-27 (2013)
EN 60255-1 (2009)
—
Table 28. EMC compliance
Description
Value
EMC directive
2004/108/EC
Standard
EN 60255-26 (2013)
—
Table 29. RoHS compliance
Description
Value
Complies with RoHS directive 2002/95/EC