1MRS750915-MUM
REM 54_
43
Machine Terminal
Technical Reference Manual, General
machine terminal includes virtual analog channels (refer to section “Calculated
analog channels” on page 47) for calculating the neutral current and residual voltage
from phase currents and voltages.
Each analog channel is separately configured with the Relay Configuration Tool.
Both the measuring unit for each analog channel and the type of signal to be
measured are to be configured.
The letters b and c after the signal type are used to distinguish between signals of the same type.
Table 5.1.6-1
Physical analog channels of the machine terminals
Measuring units
Ch
No.
Current Transformer
(CT)
Voltage Transformer
(VT)
Rogowski coil/-
sensor (RS)
Voltage
divider (VD)
General
measure-
ment
Signal type (selectable
alternatives)
1
RS 1...10
VD 1...10
Gen. meas.
1...3
Not in use,
I
L1
, I
L2
, I
L3
,
I
L1b,
I
L2b,
I
L3b,
U
1
, U
2
, U
3
,
U
1b
, U
2b
, U
3b
, U
1c
,
GE1, GE2, GE3
2
Current Transformer
CT1 (I
n
= 1 A/5 A)
RS 1...10
VD 1...10
Gen. meas.
1...3
Not in use,
I
L1
, I
L2
, I
L3
,
I
L1b,
I
L2b,
I
L3b,
I
0
, I
0b
,
U
1
, U
2
, U
3
,
U
1b
, U
2b
, U
3b
, U
1c
,
GE1, GE2, GE3
3
Current Transformer
CT2 (I
n
= 1 A/5 A)
4
Current Transformer
CT3 (I
n
= 1 A/5 A)
5
Current Transformer
CT4 (I
n
= 1 A/5 A)
Voltage Transformer
VT1 (U
n
=100V/
110V/115V/120V)
RS 1...10
VD 1...10
Gen. meas.
1...3
Not in use,
I
L1
, I
L2
, I
L3
,
I
L1b,
I
L2b,
I
L3b,
I
0
, I
0b
,
U
12
, U
23
, U
31
,
U
12b
, U
23b
, U
31b
, U
12c
,
U
1
, U
2
, U
3
,
U
1b
, U
2b
, U
3b
,
U
1c
, U
0
, U
0b
,
GE1, GE2, GE3
6
Current Transformer
CT5 (I
n
= 0.2 A/1 A)
Voltage Transformer
VT1 or VT2
(U
n
=100V/110V/
115V/120V)
Not in use,
I
L1
, I
L2
, I
L3
,
I
L1b,
I
L2b,
I
L3b,
I
0,
I
0b
,
U
12
, U
23
, U
31
,
U
12b
, U
23b
, U
31b
, U
12c
,
U
1
, U
2
, U
3
,
U
1b
, U
2b
, U
3b
, U
1c
,
U
0
, U
0b
7
Current Transformer
CT4, CT5 or CT6
(I
n
= 1 A/5 A)
Voltage Transformer
VT1 (U
n
=100V/
110V/115V/120V)
RS 1...10
VD 1...10
Gen. meas.
1...3
Not in use,
I
L1
, I
L2
, I
L3
,
I
L1b,
I
L2b,
I
L3b,
I
0
, I
0b
,
U
12
, U
23
, U
31
,
U
12b
, U
23b
, U
31b
, U
12c
,
U
1
, U
2
, U
3
,
U
1b
, U
2b
, U
3b
, U
1c
,
U
0
, U
0b
,
GE1, GE2, GE3
8
Current Transformer
CT5, CT6 or CT7
(I
n
= 1 A/5 A)
Voltage Transformer
VT2 (U
n
=100V/
110V/115V/120V)
9
Current Transformer
CT6, CT7 or CT8
(I
n
= 1 A/5 A)
Voltage Transformer
VT3 (U
n
=100V/
110V/115V/120V)
10
Voltage Transformer
VT4 (U
n
=100V/
110V/115V/120V)
RS 1...10
VD 1...10
Gen. meas.
1...3
Not in use,
I
L1
, I
L2
, I
L3
,
I
L1b,
I
L2b,
I
L3b,
U
12
, U
23
, U
31
,
U
12b
, U
23b
, U
31b
, U
12c
,
U
1
, U
2
, U
3
,
U
1b
, U
2b
, U
3b
, U
1c
,
U
0
, U
0b
,
GE1, GE2, GE3
Содержание REM 54 Series
Страница 1: ...Machine Terminal REM 54_ Technical Reference Manual General ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 22: ...22 ...
Страница 26: ...26 ...
Страница 92: ...92 ...
Страница 94: ...94 ...
Страница 102: ...102 ...
Страница 104: ...104 ...
Страница 108: ......
Страница 109: ......