1MRS750915-MUM
REM 54_
55
Machine Terminal
Technical Reference Manual, General
PO3conn_b
Fig. 5.1.8.2.-2 Double-pole power outputs (PO)
If the power outputs BIO2_7_PO3... BIO2_7_PO6 are used as single-pole outputs,
the object to be controlled is electrically connected in series with the two relay
contacts to provide sufficient breaking capacity, see the following figure.
PO2conn_b
Fig. 5.1.8.2.-3 Single-pole power outputs (PO)
Signal outputs (SO)
The signalling relay outputs (BIO1_5_SO_) are not heavy-duty outputs and thus
they cannot be used for controlling for example a circuit breaker. Available relay
contacts are either Normally Open or Normally Open/Normally Closed type (NO or
NO/NC), see the following figure. These outputs can be used for alarming and other
signalling purposes.
nonc_b
Fig. 5.1.8.2.-4 Signal outputs (SO)
+
-
CB
e.g.
BIO2_7_PO3...
BIO2_7_PO6
+
-
CB
e.g.
BIO2_7_PO3...
BIO2_7_PO6
NO/NC
NO
e.g.
PS1_4_SO1
e.g.
BIO1_5_SO1