Table 18: Default connections for binary inputs when the analog input is equipped
with AIM0013
Binary input
Default usage
Connector pins
X110-BI1
Circuit breaker closed position indication
X110:1,5
X110-BI2
Circuit breaker open position indication
X110:2,5
X110-BI3
Circuit breaker truck in (service position) indica-
tion
X110:3,5
X110-BI4
Circuit breaker truck out (test position) indica-
tion
X110:4,5
X110-BI5
MCB open
X110-6,10
X110-BI6
Control off
X110:7,10
X110-BI7
Earthing switch closed indication
X110:8,10
X110-BI8
Earthing switch open indication
X110:9,10
Table 19: Default connections for binary inputs when the analog input is equipped
with SIM0002/SIM0005
Binary input
Default usage
Connector pins
X110-BI1
Circuit breaker closed position indication
X110:1,5
X110-BI2
Circuit breaker open position indication
X110:2,5
X110-BI3
Circuit breaker truck in (service position) indica-
tion
X110:3,5
X110-BI4
Circuit breaker truck out (test position) indica-
tion
X110:4,5
X110-BI5
-
X110:6,10
X110-BI6
Control off
X110:7,10
X110-BI7
Earthing switch closed indication
X110:8,10
X110-BI8
Earthing switch open indication
X110:9,10
Table 20: Default connections for binary outputs
Binary input
Default usage
Connector pins
X100-PO1
Close circuit breaker
X100:6,7
X100-PO2
-
X100:8,9
X100-SO1
Voltage measurement high value warning
X100:10,11,(12)
X100-SO2
Current measurement high value warning
X100:13,14
Table continues on the next page
1MRS758580 C
Merging unit variants
SMU615
Application Manual
51