Figure 6: HSR solution
2.7.2
Process bus
Process bus IEC 61850-9-2 defines the transmission of Sampled Measured Values
within the substation automation system. International Users Group created a
guideline IEC 61850-9-2 LE that defines an application profile of IEC 61850-9-2
to facilitate implementation and enable interoperability. Process bus is used for
distributing process data from the primary circuit to all process bus compatible
devices in the local network in a real-time manner. The data can then be processed
by any protection relay to perform different protection, automation and control
functions.
With process bus the galvanic wiring for sharing busbar voltage value can be
replaced with Ethernet communication. Transmitting measurement samples over
process bus brings also higher error detection because the signal transmission is
automatically supervised. Additional contribution to the higher availability is the
possibility to use redundant Ethernet network for transmitting SMV signals.
1MRS758580 C
SMU615 overview
SMU615
Application Manual