Channel
ID text
Level trigger mode
61
-
-
62
-
-
63
-
-
64
-
-
3.3.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements.
The analog channels have fixed connections to the different function blocks inside
the merging unit’s application configuration. However, the 12 analog channels
available for the disturbance recorder function are freely selectable as a part of
the disturbance recorder’s parameter settings.
Phase currents are fed to the merging unit from a current transformer or a current
sensor depending on the order options. Residual current is fed to the merging unit
either from residually connected CTs, an external core balance CT or neutral CT.
Phase voltages are fed to the merging unit from a voltage transformer or a voltage
sensor depending on the order options.
3.3.3.1
Functional diagrams for local and remote control
The functional diagrams describe the merging unit's functionality in detail and
according to the factory set default connections.
Local & remote control
General logic state TRUE and FALSE
Control
O:25|T:2.5|I:0
CTRL_OFF
CTRL_LOC
CTRL_STA
CTRL_REM
CTRL_ALL
OFF
LOCAL
STATION
REMOTE
ALL
BEH_TEST
BEH_BLK
TRUE
NOT
O:24|T:2.5|I:0
IN
OUT
NOT
O:36|T:2.5|I:3
IN
OUT
TRUE
TRUE
FALSE
FALSE
Figure 17: Local and remote control mode function
Merging unit variants
1MRS758580 C
44
SMU615
Application Manual
Содержание Relion SMU615