Condition and supervision functions
Table 66. Circuit-breaker condition monitoring (SSCBR)
Characteristic
Value
Current measuring accuracy
±1.5% or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0%
(at currents in the range of 10…40 × I
n
)
Operate time accuracy
±1.0% of the set value or ±20 ms
Travelling time measurement
+10 ms / -0 ms
Table 67. Current circuit supervision (CCSPVC)
Characteristic
Value
Operate time
1)
<30 ms
1)
Including the delay of the output contact
Table 68. Current circuit supervision (CCSPVC) main settings
Parameter
Function
Value (Range)
Step
Start value
CCSPVC
0.05...0.20 × I
n
0.01
Max operate current
CCSPVC
1.00...5.00 × I
n
0.01
Table 69. Fuse failure supervision (SEQSPVC)
Characteristic
Value
Operate time
1)
NPS function
U
Fault
= 1.1 × set
Neg Seq voltage
Lev
<33 ms
U
Fault
= 5.0 × set
Neg Seq voltage
Lev
<18 ms
Delta function
ΔU = 1.1 × set
Voltage change rate <30 ms
ΔU = 2.0 × set
Voltage change rate <24 ms
1)
Includes the delay of the signal output contact, f
n
= 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Table 70. Runtime counter for machines and devices (MDSOPT)
Description
Value
Motor runtime measurement accuracy
1)
±0.5%
1)
Of the reading, for a stand-alone relay, without time synchronization
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
42
ABB
Содержание RELION REV615
Страница 1: ... RELION 615 SERIES Capacitor Bank Protection and Control REV615 Product Guide ...
Страница 58: ...58 ...
Страница 59: ......